beautypg.com

Installation instructions, Exhaust inducer (blower assy.), Circulating pump – American Water Heater ABCG3 User Manual

Page 7: Dishwashing machine requirement, Uncrating, Locating the heater

background image

7

IGNITION CONTROL BOARD - FIGURE 3

EXHAUST INDUCER (BLOWER ASSY.)

All models are equipped with an exhaust inducer. The inducer
assists in drawing in fresh air to the unit for combustion and
then assists in dispensing the combustion by-products into the

venting leading outside.

The exhaust inducer is equipped with a gravity controlled damper to
reduce the amount of heat loss through the flue, improving efficiency.

EXHAUST INDUCER - FIGURE 4

CIRCULATING PUMP

A circulating pump is used when a system requires a circulating
loop or there is a storage tank used in conjunction with the
heater. Refer to the piping diagrams in this manual for electrical

hookup information and install in accordance with the current
version of the National Electrical Code ANSI/NFPA No. 70.

Only all bronze circulating pumps are used with commercial
water heaters.

Although circulating pumps are oiled and operated by the
manufacturer some circulating pumps must be oiled again
before operating. Please refer to manufacturer’s instructions.

DISHWASHING MACHINE REQUIREMENT

These appliances meet the National Sanitation Foundation

Standard for sanitary installations when used with the following
leg kit, Part No. 6570-7.

All dishwashing machines meeting the National Sanitation
Foundation requirements are designed to operate with water flow
pressures between 15 and 25 psi. Flow pressures above 25 psi, or

below 15 psi, will result in improperly sanitized dishes. Where
pressures are high, a water pressure reducing or flow regulating
control valve should be used in 180

0

F line to the dishwashing machine,

and should be adjusted to deliver water between these limits.

The National Sanitation Foundation also recommends

circulation of 180

0

F water. Where this is done, the circulation

should be very gentle so that it does not cause any unnecessary
turbulence inside the water heater. The circulation should be

just enough to provide 180

0

F water at the point of take-off to the

dishwashing machine. Adjust flow by means of the plug cock in
the circulating line.

INSTALLATION INSTRUCTIONS

REQUIRED ABILITY

INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES
ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN
THE FIELD INVOLVED. PLUMBING, AIR SUPPLY, VENTING, GAS
SUPPLY AND ELECTRICAL WORK ARE REQUIRED.

WARNING

FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT
IN SERIOUS PERSONAL INJURY OR DEATH.

UNCRATING

The heater is shipped with the inducer already installed. The
wiring conduit runs from the thermostat to the inducer. Before
turning unit on, check to make sure the wiring conduit is securely
plugged into the inducer.

LOCATING THE HEATER

When installing the heater, consideration must be given to proper
location. Location selected should be as close to the stack or
chimney as practicable, with adequate air supply and as
centralized with the piping system as possible.

WARNING

THERE IS A RISK IN USING FUEL BURNING APPLIANCES SUCH
AS GAS WATER HEATERS IN ROOMS, GARAGES OR OTHER

AREAS WHERE GASOLINE, OTHER FLAMMABLE LIQUIDS OR
ENGINE DRIVEN EQUIPMENT OR VEHICLES ARE STORED,
OPERATED OR REPAIRED. FLAMMABLE VAPORS ARE HEAVY

AND TRAVEL ALONG THE FLOOR AND MAY BE IGNITED BY
THE HEATER’S PILOT OR MAIN BURNER FLAMES CAUSING
FIRE OR EXPLOSION. SOME LOCAL CODES PERMIT

OPERATION OF GAS APPLIANCES IN SUCH AREAS IF THEY
ARE INSTALLED 18” OR MORE ABOVE THE FLOOR. THIS MAY
REDUCE THE RISK IF LOCATION IN SUCH AN AREA

CANNOT

BE AVOIDED.

DO NOT INSTALL THIS WATER HEATER DIRECTLY ON A

CARPETED FLOOR. A FIRE HAZARD MAY RESULT.

Instead the

water heater must be placed on a metal or wood panel extending
beyond the full width and depth by at least 3 inches in any direction.

If the heater is installed in a carpeted alcove, the entire floor
shall be covered by the panel. Also, see the DRAINING
requirements in MAINTENANCE Section.

THE HEATER SHOULD BE LOCATED OR PROTECTED SO IT IS
NOT SUBJECT TO PHYSICAL DAMAGE BY A MOVING VEHICLE.

WARNING

FLAMMABLE ITEMS, PRESSURIZED CONTAINERS OR ANY
OTHER POTENTIAL FIRE HAZARDOUS ARTICLES MUST
NEVER BE PLACED ON OR ADJACENT TO THE HEATER. OPEN
CONTAINERS OR FLAMMABLE MATERIAL SHOULD NOT BE
STORED OR USED IN THE SAME ROOM WITH THE HEATER.

THE HEATER MUST NOT BE LOCATED IN AN AREA WHERE IT
WILL BE SUBJECT TO FREEZING.

LOCATE IT NEAR A FLOOR DRAIN. THE HEATER SHOULD BE
LOCATED IN AN AREA WHERE LEAKAGE FROM THE HEATER
OR CONNECTIONS WILL NOT RESULT IN DAMAGE TO THE
ADJACENT AREA OR TO LOWER FLOORS OF THE
STRUCTURE.

WHEN SUCH LOCATIONS CANNOT BE AVOIDED, A SUITABLE
METAL DRAIN PAN SHOULD BE INSTALLED UNDER THE
HEATER.

Such pans should be fabricated with sides at least 2"