beautypg.com

Table 6. technical data venting – American Water Heater ABCG3 User Manual

Page 10

background image

10

TYPE B GAS VENT

Multiple Gas Fired Tank-Type Heaters

When venting multiple tank type heaters using Type B
vent pipe, follow the installation diagram (figure 4) and
tables below which give sizing and data based upon
NFPA 54/ANSI Z223. 1992.

TABLE 6. TECHNICAL DATA VENTING

MODEL BCG370T1205NOX
Input: 120,000 Btu/hr

Total Vent Height (Feet)

Vent Connector Size: 5 inches

6

8

10

15

20

30

50

100

Input Btu/hr

Rise

Vent Connector Diameter (Inches)

120,000

1 Ft.

6

6

5

5

5

5

5

5

120,000

2 Ft.

5

5

5

5

5

5

5

5

120,000

3 Ft.

5

5

5

5

5

5

5

5

Number of

Combined Input

BCG370T1205NOX

in Thousands of Btu/hr

Manifold and Common Vent Diameter (Inches)

2

240,000

7

7

6

6

6

6

6

6

3

360,000

8

8

7

7

7

6

6

6

4

480,000

9

9

9

8

8

7

7

6

MODEL BCG380T1506NOX
Input: 154,000 Btu/hr

Total Vent Height (Feet)

Vent Connector Size: 6 inches

6

8

10

15

20

30

50

100

Input Btu/hr

Rise

Vent Connector Diameter (Inches)

154,000

1 Ft.

6

6

6

6

6

6

6

6

154,000

2 Ft.

6

6

6

6

6

6

6

6

154,000

3 Ft.

6

6

6

6

6

6

6

6

Number of

Combined Input

BCG380T1506NOX

in Thousands of Btu/hr

Manifold and Common Vent Diameter (Inches)

2

308,000

7

7

6

6

6

6

6

6

3

462,000

8

8

7

7

7

6

6

6

4

616,000

9

9

9

8

8

7

7

6

MODEL BCG3100T1806NOX, BCG3100T1996NOX, & (A)BCG3100T2006NOX
Input: 180,000, 190,000 and 199,000 Btu/hr

Total Vent Height (Feet)

Vent Connector Size: 6 inches

6

8

10

15

20

30

50

100

Input Btuh/hr

Rise

Vent Connector Diameter (Inches)

180,000

1 Ft.

7

7

6

6

6

6

6

6

190,000

1 Ft.

7

7

7

6

6

6

6

6

199,000

1 Ft.

7

7

7

6

6

6

6

6

180,000

2 Ft.

6

6

6

6

6

6

6

6

190,000

2 Ft.

7

6

6

6

6

6

6

6

199,000

2 Ft.

7

7

6

6

6

6

6

6

180,000

3 Ft.

6

6

6

6

6

6

6

6

190,000

3 Ft.

6

6

6

6

6

6

6

6

199,000

3 Ft.

6

6

6

6

6

6

6

6

Number of

Combined Input

(A)BCG3 Heaters

in Thousands of Btu/hr

Manifold & Common Vent Diameter (Inches)

360,000

7

7

6

6

6

6

6

6

2

380,000

7

7

7

6

6

6

6

6

398,000

6

7

7

6

6

6

6

6

540,000

7

6

6

6

6

6

6

6

3

570,000

7

6

6

6

6

6

6

6

597,000

6

7

6

6

6

6

6

6

720,000

6

6

6

6

6

6

6

6

4

760,000

6

6

6

6

6

6

6

6

796,000

6

6

6

6

6

6

6

6