Charging phases, 19 gb – AEG Micro-Processor Charging Unit LP 3.8 User Manual

Page 19

background image

19

GB

Step 2: Main charging
Charging to 80 % of power:
1. the charger provides the battery with a constant

charging capacity of max. 3.8 a until the terminal

voltage reaches a value of 12.8 V.

2. the charger provides the battery with a constant

charging capacity of max. 3.0 a until the terminal

voltage reaches a value of 14.1 V. By reducing the

maximum available charging capacity, the heating

of the battery is minimised. this leads to a reduction

of gas build-up within the battery.

Step 3: Absorption
the charger provides the battery with a constant

charging capacity of max. 0.8 a until the terminal

voltage has reached a value of 14.4 V. the battery is

fully charged. subsequently, the charger automatically

switches to the buffer charging phase.

Step 4: Buffer charging
Buffer charging starts after the battery is completely

charged (LED FULL (13) lights up).
in this mode the connected battery is constantly

charged with approx. 100 ma power. as soon as

the terminal voltage of the battery monitored by the

charger falls below 12.8 V, maintenance charging is

automatically activated.

Step 5: Maintenance charging
in this mode the connected battery is constantly

charged with approx. 800 ma power until the terminal

voltage reaches 14.4 V. after reaching this terminal

voltage the charger will automatically switch back to

buffer charging.
this procedure continues cyclically for as long as

possible, depending on the monitored terminal voltage

and is not terminated until the charger is disconnected.

Due to this change of the charge cycle the battery is

kept at the highest possible charging level.

Recovering a used battery

the charger can save most used batteries with volt-

ages up to at least 7.5 ± 0.5 V

Before starting the charging procedure the charger

automatically identifies the battery voltage

thanks to the safety circuit the charger does not

start charging if the voltage is below 7.5 ± 0.5 V

in the voltage area of 7.5 ± 0.5 V to 10.5 ± 0.5 V

the charger initiates an impulse charging procedure

if the voltage increases to more than

10.5 ± 0.5 V, the charger switches to the previously

selected normal mode for faster and safer charging.

CHargiNg pHasEs

the charger performs a fully automated 5-level charge

cycle.

Charging

with a

high rate

Charging

with an

intermediate

rate

absorption

0.8 a

Buffer

charging

100 ma

maintenance

charging

0.8 a

below 12.8 V

14.4 V

14.4 V

14.1 V

12.8 V

10,5 V

3.8 a

3.0 a

impulse

main charging

Voltage V

15.5

13.5

11.5

9.5

7.5

0

Diagnosis

and

corrective

actions

Step 1: Diagnosis and corrective actions
Diagnosis function during which the battery status is

automatically checked and the voltage identified.