Error messages, Ce compliance, Warranty – Young Marine Wind Tracker Model 06206 User Manual
Page 4: Specifications
Page 3
06206-90(G)
BRIGHTNESS
Adjust display brightness by pressing and holding the left BRIGHT
key.
MAXIMUM or WIND DIRECTION DISPLAY
MAXIMUM WIND SPEED GUST or numerical WIND DIRECTION
appears during operation depending on Right Display Window
(dSP) parameter setting. Maximum gust may be reset during normal
operation by pressing and holding the RESET key for 1 second.
REMOTE DISPLAYS
The Marine Wind Tracker may be configured as a remote display by
setting the Sensor Input for serial input (InP=SEr) and connecting
the RS-485 terminals to a source providing a $WIMWV NMEA
wind speed and direction string. This may be any valid NMEA
source including another Wind Tracker operating as a master,
a Young wind sensor or interface sending the NMEA string, or a
shipboard system.
With a Marine Wind Tracker as the NMEA source, use these settings:
MASTER: Sensor InP = any non-serial device.
REMOTE: Sensor InP = SEr
Connect one master with up to 16 remote displays via RS-485
terminals as shown in wiring diagrams. Remote Marine Wind
Trackers display exactly the same information as the master
including alarm states. MAX RESET and all display features are
controlled by the master unit only. Brightness can be adjusted
independently at each Marine Wind Tracker display.
VOLTAGE OUTPUTS
Calibrated voltage outputs for wind speed and direction are updated
16 times per second. Wind Speed 0-100 m/s = 0.00 to 5.00 VDC.
Wind Direction may be scaled for either 0-360 or 0-540 degrees =
0.00 to 5.00 VDC by setting the Direction (dir) parameter.
4-20 mA INPUTS
The Wind Tracker accepts 4-20 mA Line Driver inputs with either
0-50 m/s or 0-100 m/s scaling (Ldi and Ld2 input settings). Connect
as shown in wiring diagram. The back-panel switch labeled 4-20
mA must be in the UP position. 24VDC power is recommended
for most 4-20 mA installations.
POWER CONNECTIONS
The Marine Wind Tracker operates from 12 to 30 VDC. Power
may be connected via the coaxial jack or terminals. See wiring
diagrams for examples.
ERROR MESSAGES
Ldi
Err
4-20 mA (line driver) signal is missing or outside
an acceptable range. Verify connections, signal,
and 4-20 mA switch in UP position.
SEr
Err
Unit set to receive RS-485 serial signal (inP=SEr
or 09), but no serial data detected. Verify NMEA
source is working. Verify connections.
Declaration of Conformity
R. M. Young Company
2801 Aero Park Drive
Traverse City, MI 49686 USA
Model 06206 Wind Tracker
The undersigned hereby declares on behalf of R. M.
Young Company that the above-referenced product, to
which this declaration relates, is in conformity with the
provisions of:
Council Directive 2004/108/EC (December 15, 2004)
on Electromagnetic Compatibility
David Poinsett
R&D Manager
CE COMPLIANCE
This product complies with European CE EMC Directive.
Shielded cable must be used.
WARRANTY
The Wind Tracker is warranted to be free of defects in materials
and construction for a period of 12 months from date of purchase.
Coverage is limited to repair or replacement of defective unit.
SPECIFICATIONS
Size:
144 mm (5.65 in) x 144 mm (5.65 in) x 36 mm (1.4 in)
Panel Cutout: 138 mm (5.43 in) x 138 mm (5.43 in)
Sensors:
Wind Monitor-MA (05), Wind Monitor (05),
Wind Monitor HD (Hd), Wind Monitor-SE (SEr),
Ultrasonic Anemometer (SEr), Wind Monitor-JR
(04), Wind Sentry (03), Wind Monitor HD (Hd)
Accuracy:
±0.6% Full Scale
NMEA Serial Input & Output:
$WIMWV, ddd, R, sss, u, A*c
ddd wind direction in degrees
sss wind speed (ss.s for m/s)
u units (N knots, K km/hr, M m/s, S statute mph)
c NMEA checksum
Other inputs: 4-20 mA (0-360 deg, Ldi 0-50 m/s, Ld2 0-100 m/s)
Other outputs: 0-5 VDC = 0-360° or 0-540°
0-5 VDC = 0-100 m/s
Alarm Relays: Normally Open contacts for WS and WD
Contact rating 24 VAC or 30 VDC maximum
5A resistive, 2A inductive maximum
Input Power: 12-30 VDC, 3.5 W
Weight:
1.0 lb (0.45 kg) without AC adapter