9. Error codes
When detecting an operating state which is not permissible, the device will display an error code
The following error codes are defined:
Error presumed
cause Solution
Err 1
- Input signal to high
- The input sighnal must be within
- Exceeding of the measuring
- Sensor broken
the limits
range
- Sensor shorted
- Check sensor, transducer / transmitter
- Check device configuration
- Reset the counter
Err 2
- Input signal to low /negative
- The input sighnal must be within
- Values below measuring
- Current below 4 mA
the limits
range
- Sensor shorted
- Check sensor, transducer/ transmitter
- Sensor broken
- Check device configuration
- Counter underflow
- Reset the counter
Err 3
- Incorrect scale
- The error message will be reset if the
- Display range has been
- Counter overflow
display value is below 9999
exceeded
Err 4
- Incorrect scale
- The error message will be reset if the
- Values below display range
- Counter underflow
display value is above -1999
- Defective device
- Reset the counter
Err 7
- Valid operation temperature
- Stay within valid temperature range
- System error
has been exceeded
- Exchange the defective device
Err 9
- Sensor broken /shorted
(PT100)
- Check sensor
- Sensor defective
-Sensor broken (Thermocouple)
Err 11
- Incorrect scale
- Check settings and input signal
- Value could not be calculated