Operating instructions digital indicator di15, Interface mode, Selection of the output function – WIKA DI15 User Manual
Page 18
Operating Instructions Digital Indicator DI15
V1.3
•
02/2011
- 18 -
- Press button 1 to validate your selection. The display shows “Li“ again.
Now your device is adjusted to your signal source. The only thing left to do is to adjust the outputs of the
device.
- When pressing button 1 again, the display will show “outP“. (Output)
For configuring the outputs of the DI15, please follow the instructions shown in chapter 4.8.
4.7. Interface mode
When the device is in the interface mode it won’t make any measurements by itself. The value shown in the device’s dis-
play is sent via serial interface. But the switching and alarm functions of the displayed value are still available. The
EASY-
BUS
-Address of the device needed for the communication can be set manually with the device itself or with the help of an
EASYBUS
-software (like EbxKonfig). Please note, when carrying out an
EASYBUS
-system-initialisation the device’s address
will be reset automatically.
This chapter describes how to configure the device as an
EASY
BUS
-display.
This instruction requires that you selected “SEri“ as your desired input type like it is explained in chapter 4.1
The device has to display “InP“.
- When pressing button 1 again, the device will display “Adr“ (address).
- Use button 2 and button 3 to select the desired address [0 ... 239] of the device.
- Press button 1 to validate the selected device address. The display shows “Adr“ again.
You don’t need any further configuration except the outputs.
- When pressing button 1 again, the device will be displaying “outP“ (output).
For configuring the outputs please follow the instructions given in chapter 4.8.
4.8. Selection of the output function
- After configuration of the input (chapter 4.2 – 4.7) you have to select the output function.
The display shows “outP“ (output).
- Use button 2 and button 3 (middle resp. right button) to select the desired output-function.
Description
Function
To select as
output
See chapter
Output 1
Output 2
No output, device is used
as display unit
--- ---
no
--
2-point-controller digital
2-point-
controller
---
2P
5.1
3-point-controller
digital
2-point-
controller
digital
2-point-
controller
3P
5.1
2-point-controller with
Min-/Max-alarm
digital
2-point-
controller
Min-/Max-alarm
2P.AL
5.2
Min-/Max-alarm,
common
--- Min-/Max-alarm
AL.F1
5.3
Min-/Max-alarm,
individual
Max-alarm Min-alarm
AL.F2
5.3
- Press button 1 to validate the selected output function. The display shows “outP“ again.
Depending on your output function setting, it may be possible that one or more settings described below
won’t be available.