Operating Instructions Digital Indicator DI15

V1.3

02/2011

- 18 -

- Press button 1 to validate your selection. The display shows “Li“ again.

Now your device is adjusted to your signal source. The only thing left to do is to adjust the outputs of the
device.

- When pressing button 1 again, the display will show “outP“. (Output)

For configuring the outputs of the DI15, please follow the instructions shown in chapter 4.8.

4.7. Interface mode

When the device is in the interface mode it won’t make any measurements by itself. The value shown in the device’s dis-

play is sent via serial interface. But the switching and alarm functions of the displayed value are still available. The

EASY-

BUS

-Address of the device needed for the communication can be set manually with the device itself or with the help of an

EASYBUS

-software (like EbxKonfig). Please note, when carrying out an

EASYBUS

-system-initialisation the device’s address

will be reset automatically.

This chapter describes how to configure the device as an

EASY

BUS

-display.

This instruction requires that you selected “SEri“ as your desired input type like it is explained in chapter 4.1
The device has to display “InP“.

- When pressing button 1 again, the device will display “Adr“ (address).

- Use button 2 and button 3 to select the desired address [0 ... 239] of the device.

- Press button 1 to validate the selected device address. The display shows “Adr“ again.

You don’t need any further configuration except the outputs.

- When pressing button 1 again, the device will be displaying “outP“ (output).

For configuring the outputs please follow the instructions given in chapter 4.8.

4.8. Selection of the output function

- After configuration of the input (chapter 4.2 – 4.7) you have to select the output function.

The display shows “outP“ (output).

- Use button 2 and button 3 (middle resp. right button) to select the desired output-function.

Description

Function

To select as

output

See chapter

Output 1

Output 2

No output, device is used
as display unit

--- ---

no

--

2-point-controller digital

2-point-
controller

---

2P

5.1

3-point-controller

digital
2-point-
controller

digital
2-point-
controller

3P

5.1

2-point-controller with
Min-/Max-alarm

digital
2-point-
controller

Min-/Max-alarm

2P.AL

5.2

Min-/Max-alarm,
common

--- Min-/Max-alarm

AL.F1

5.3

Min-/Max-alarm,
individual

Max-alarm Min-alarm

AL.F2

5.3

- Press button 1 to validate the selected output function. The display shows “outP“ again.

Depending on your output function setting, it may be possible that one or more settings described below
won’t be available.