Operating instructions digital indicator di15, Minimum/maximum-alarm (individual or common) – WIKA DI15 User Manual
Page 23
![background image](/manuals/465936/23/background.png)
Operating Instructions Digital Indicator DI15
V1.3
•
02/2011
- 23 -
5.3. Minimum/maximum-alarm (individual or common)
This chapter describes how to configure the device‘s alarm boundaries for min-/max-alarm-monitoring.
This instruction demands that you selected “AL.F1“ resp. “AL.F2“ as your desired output function like it is
explained in chapter 4.8.
- Press button 1
(if not already done)
, the device will be displaying “AL.Hi“. (maximum alarm-value)
- Use button 2 and button 3 to set the desired value, the device should turn on its maximum-alarm.
- Press button 1 to validate your selection. The display shows “AL.Hi“ again.
- When pressing button 1 again, the device will be displaying “AL.Lo“. (minimum alarm-value)
- Use button 2 and button 3 to set the desired value, the device should turn on its minimum-alarm
- Press button 1 to validate your selection. The display shows “AL.Lo“ again.
- When pressing button 1 again, the device will be displaying “A.dEL“. (delay of the alarm-function)
- Use button 2 and button 3 to set the desired delay of the alarm-function.
Note:
The unit of the value to be set is in [sec.]. The device will turn on the alarm after minimum
resp. maximum alarm value was active for the delay-time you have set.
- Press button 1 to validate the delay time. The display shows “A.dEL“ again.
Example: You want to have a temperature alarm-monitoring of a greenhouse. The alarm should start when
the temperature rises above 50°C resp. falls below 15°C.
Therefore your settings will be 50°C for the maximum alarm-value “AL.HI“ and 15°C for the mini-
mum
alarm-value
“AL.Lo“.
The alarm will start after the temperature rises above 50°C and stays above 50°C for the entered
delay time resp. after it had been falling below 15°C and stays below 15°C for the entered delay
time.
Please note that the alarm-outputs are inverted! This means, that the output will be active when there is no
alarm!
Now you finished configuring your device. Press button 3 to switch over to display the measuring value.