4. Requirements for use ... / 5. Switch contacts

Temperature class of the
ambient atmosphere
(ignition temperature)

Permissible maximum
medium temperature
(in the pressure system)

T 6 ( > 85 °C)

+70 °C

T 5 ( > 100 °C)

+85 °C

all other temperature classes

+100 °C

Attention! In the case of gaseous substances, the temperature may

increase due to compression warming. In these cases it may be

necessary to throttle the rate of change of pressure or reduce the

permissible temperature of the pressure medium.

Table 1: Permissible medium temperature

5. Switch contacts

Switching function

The switching function is identified by the code ’3’.

851.

3 = SPDT contact

Electrical load

Max. switching voltage: 24 VDC / VAC

Max. load:

10 W

Max. current:

0.5 A

Wiring details

 The electrical connections must only be made by qualified

personnel

 Cable output 3 m long, conductor cross section 0.14 mm

2

,

flying leads

 The terminal assignment is stated on the pressure gauge's

connection plate

The gauges do not have integrated overcurrent

protection. If overcurrent protection is required,

this has to be provided externally.

 The instruments must be connected to the equipotential bonding

of the plant!