Permissible vibration load at the mounting point

The instruments should always be installed in locations free from vibration.

If necessary, it is possible to isolate the instrument from the mounting point

by installing a flexible connection line between the measuring point and the
pressure gauge and mounting the instrument on a suitable bracket.

If this is not possible, the following limit values must not be exceeded:

Dry gauges:

Frequency range < 150 Hz

(Model 732)

Acceleration < 0.7 g (7 m/s

)

Liquid-filled gauges:

Frequency range < 150 Hz

(Model 733)

Acceleration < 4 g (40 m/s

)

The liquid filling must be checked on a regular basis.
The liquid level must not drop below 75 % of the gauge diameter.

4. Switch contacts

EC-type examination certificates

Standard version Model 831.XX

PTB 99 ATEX 19 X (Appendix ) and ZELM 03 ATEX 018 X (Appendix 4)
Depending on the number of switches and on the case diameter either
Model SJ2-N... or Model SJ3.5-...-N... is used.

Safety pattern version Models 831.XX - SN or - S1N

PTB 00 ATEX 049 X (Appendix 3) and ZELM 03 ATEX 018 X (Appendix 4
Depending on the number of switches and on the case diameter either
Models SJ 2-SN..., SJ 2-S1N..., SJ 3.5-SN.. or SJ 3.5-S1N... are used.

The built-in sensor type is stated on the product label of the pressure gauge.

Wiring details

The electrical connections must only be made by qualified personnel
Connection of the switches via screw terminals in the terminal box
Conductor cross section max. 1.5 mm

The terminal assignment is stated on the connection plate of the

pressure gauge

The instruments must be connected to the equipotential bonding of the plant