beautypg.com

Caution – Comfort-Aire FMG****F1E Series User Manual

Page 6

background image

6

18"

(457 mm)

24” Clearance from

nearest wall or

partition

Full Louvered

Door

Wall

Mount

Closet

Installation

Alcove

Installation

6”

(152mm)

Typical Closet Door

with Return Air Grill

Installed

OR

Recessed

Wall

Wall

2-Piece

Mounting

Bracket

24” Clearance from

nearest wall or

partition

Figure 1. Unit Installation

CAUTION:

This unit uses refrigerant R-410A. DO NOT use
any other refrigerant in this unit. Use of another
refrigerant will damage the unit.

• Every effort should be made by the installer to ensure

that the field installed refrigerant containing components
of the system have been installed in accordance with
these instructions and sound installation practices to
insure reliable system operation and longevity.

• Always refer to the installation instructions supplied with

the outdoor unit for piping requirements. The suction
and liquid lines must be sized in accordance with the
condensing unit specifications. See Figure 4 (page 12)
for liquid and suction line locations.

• When connecting refrigerant linesets together, it is

recommended that dry nitrogen be flowing through the
joints during brazing. This will prevent internal oxidation
and scaling from occurring.

• Refrigerant tubing should be routed in a manner that

minimizes the length of tubing and the number of bends
in the tubing. It should be supported in a manner that
prevents it from vibrating or abrading during system
operation. Tubing should be kept clean of foreign debris
during installation.

• If precise forming of refrigerant lines is required, a copper

tubing bender is recommended. Avoid sharp bends and
contact of the refrigerant lines with metal surfaces.

• Refrigerant lines should be wrapped with pressure

sensitive neoprene or other suitable material where
they pass against sharply edged sheet metal.

• The FMG air handler is charged through a Schrader

valve on the end of the liquid tube. This must be removed
before brazing the line sets.

System Depressurization
1. Remove the cap from the end of the liquid line.
2. Verify pressurization by depressing the Schrader valve

on the end of the liquid line. Listen for any escaping gas.
If there is no pressure, test the unit for leakage.

• If leakage is found, clearly mark the location of the leak

and return the unit to the distributor for processing.

• If no leaks are found, the air handler may be installed.
3. Depress the valve to relieve all pressure from the coil.
4. Remove the Schrader valve housing from the end of

the liquid tube by unbrazing or using a tube cutter.

Connecting the Linesets
Notes: Before proceeding, perform steps 1 - 3 in the
System Depressurization section.
1. Route and cut both lineset tubes to proper length in

accordance with the outdoor unit specifications. Verify
the ends are round, clean, and free of any burrs.

2. Connect the suction and liquid lineset tubes.