Installation Guide APC Silcon 480kW 400V UPS

71

9.0 Appendix

9.1

Table 1. Installation Planning Data

Main Input
Breaker

Field
Wiring*

Battery Bank**

UPS Module

Service Bypass Panel

Field
Wiring

Output
Breaker

*

** Internal Batteries available for 40kW units and smaller

*

*

Q1

Q2

Q3

* Not supplied by APC

Installation Planning Data

APC Silcon Series

AC Input

Battery System DC

AC Output

Min. Input

Input

Full

I

Nom

I

Max

Load side

Heat

Power rating

Source

P (kW)

I (A)

Cable

Overcurrent

V

n

load

Disch Disch

I

n

Overcurrent Dissipation

kW

kVA

Pf

V

Hz

Nom.

Max.

Nom.

Max.

(per phase)

Protection*

(Vdc)

P(kW)

(A)

(A)

(A)

Protection*

(kW)

480

480

1

380
400
415

50/60 491.8 569.5

838.3
747.3
768.4

922.1
822.0
845.2

3//185mm

2

1000 A

2x384

505.3

658

775

727.3
695.7
666.7

800 A

15.9

COLUMN

1a

1b

1c

1d

1e

1f

1g

1h

2a

2b

2c

2d

3a

3b

4a

NOTES

3

4

1

2

9

5, 6, 13

8

12

10

11

6, 7

13

* Provided by others