4.7.5 Troubleshooting

The following table shows the solution to common problems with the operation of the Triple
Chassis

4.7.5.1 If Problems Persist

For problems not covered in the troubleshooting chart or for persistent problems, follow this
procedure:

1) Note the serial number and date of purchase of the APC Silcon Triple Chassis. Contact APC

Customer Support at the phone number or address that is listed in this manual.

2) Be prepared to provide a description of the problem. A technician will help solve the

problem over the phone, if possible, or will give you a return material authorization (RMA)
number.

3) If the APC Silcon Triple Chassis is under warranty, repairs are free of charge. If the

warranty has expired, there will be a nominal charge for repair.

AP9604S[R]

APC Silcon Triple Chassis

90

AP9606

Web/SNMP Management Card

110

AP9607

Interface Expander

45

AP9608

Out-of-Band Management Card

(Call-

UPS

II)

35

AP9612

Environmental Monitoring Card (Measure-UPSII)

60

AP9825i

Isolated Extension Cable

50

AP9830

Remote Power-Off Device

35

Problem

Possible Cause

Solution

Status LED is off

The chassis is not
receiving adequate
power.

See “Powering the APC Silcon
Triple Chassis”, and verify that you
are not exceeding current
requirements.

Status LED is flashing
quickly

The chassis has not been
configured.

Configure the Silcon Triple
Chassis. See the APC Silcon
Management Quick Start Guide
provided with your chassis or the
Web/SNMP Management Card
Installation Guide on the CD for
more information.

Status LED is flashing
slowly

The chassis is not
communicating with the
UPS.

Verify that the supplied UPS cable
is properly connected to the Triple
Chassis and to a communications
port on the UPS.

Attached management
peripheral cannot
identify UPS model or
nominal output voltage.

The management
peripheral firmware
does not support 3-phase
UPSs.

You may be able to upgrade the
firmware of the management
peripheral. Call APC Customer
Support.