beautypg.com

Options/accessories – APC SILCON 990-4053 User Manual

Page 43

background image

Options/Accessories

990-4053

Installation Guide APC Silcon 480kW 400V UPS

43

6.0 Options/Accessories

Please contact your local APC representative for information on options/accessories available
in your region. See “How to Contact APC” in this guide.

6.1

Service Bypass Panel for Single Operation

UPS

Exter-
nal
System
Input
Fuse
[A]

Max.
Pro-
spec-
tive
Short-
Circuit
Current
[kA]

System
Input/
UPS
Input
Cable
[mm2]
**

System
Output/
UPS
Output
Cable
[mm2]
**

Max.
Exter-
nal
Syste
m
Output
Fuse
[A]***

Max.
Cable
Size/
Stud
Size

Dimensions
HxWxD [mm]

Weight
[kg]

Fixing
Cen-
tres
AxB
[mm]

480

kW

1000

45

3x185

3x150

800

M12

1825x

1160x620

(680*)

250

-

***

If no external System Output fuses are available or if it has a higher value than
indicated above, System Output and UPS Output cables should be dimensioned as
System Input and UPS Input cables.

**

Sizes according to IEC 364-5-532 for PVC insulated copper cables (max. ambient
temperature: 30

o

C). Installation method B: Insulated conductors in wall conduit.

Also refer to local legal regulations.

Beware that single-phase Switch Mode Power supply loads will increase neutral
current! At a 100% SMPS load, neutral cable should be dimensioned for 200% of
phase current.

*

Depth of enclosure includes switch handles