External connection – APC SILCON 990-4053 User Manual
Page 23
External Connection
990-4053
Installation Guide APC Silcon 480kW 400V UPS
23
4.7.3.1 Order of Management Peripheral Cards
Because UPS signals are passed between management peripherals, you must install
management peripheral cards in the correct order for them to work together properly. The card
slots are numbered 1 to 3, from left to right, as viewed from the rear of the chassis. The
following table lists the management peripheral cards, their priority, and proper position.
4.7.3.2 Installing Management Peripheral Cards
To install management peripherals, perform the following steps.
1) Make sure that the chassis is powered off.
2) Install management peripheral cards into the housings on the rear of the chassis. See the
instructions supplied with the cards and the table above.
3) If you are daisy-chaining other APC external management peripherals to the APC Silcon
Triple Chassis: Connect the UPS cable (supplied with the management peripheral) to the
Monitoring port of the chassis and to the “To UPS” port of the other management peripheral
(Share-UPS, MasterSwitch, etc.). See “Daisy-chaining the APC Silcon Triple Chassis”.
4) Power the APC Silcon Triple Chassis and all external management peripherals.
4.7.3.3 Daisy-chaining the APC Silcon Triple Chassis
If you need more than the three card slots available with the APC Silcon Triple Chassis, or if
you want to use other external management peripherals, you can daisy-chain external
management peripherals together, provided that the total amperage of all installed
management peripherals — cards and external — does not exceed the supplied amperage. (See
“Determining Power Requirements:”).
Management
Peripheral Card
P/N
Priority
Position
Web/
SNMP
Management
Card
AP9606
Highest
High-numbered slot
Low-numbered slot
Out-of-Band
Management Card
(Call-
UPS
®
II)
AP9608
Second-highest
Interface Expander
AP9607
Second lowest
Environmental
Monitoring Card
(Measure-
UPS
®
II)
AP9612T
AP9612TH
Lowest
NOTICE!
If your configuration requires additional power, connect a 24V AC/DC power adapter available
from APC (part number AP9505 or AP9505i) for all models of Triple Chassis.
NOTICE!
When daisy-chaining Triple Chassis units, you may need to use a power adapter.