beautypg.com

American Dryer Corp. AD-115ES User Manual

Page 21

background image

17

a. Outside Duct Work Protection

1) To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the exhaust duct work travels vertically up

through the roof, it should be protected from the weather by using a 180° turn to point the opening

downward. In either case, allow at least twice the diameter of the duct between the duct opening and

the nearest obstruction.

IMPORTANT: DO NOT use screens or caps on the outside of opening of exhaust duct work.

2. Single Dryer Venting

a. Horizontal Venting

Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct

should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as

few turns as possible. It is suggested that the use of 90° turns in ducting be avoided; use 30° or 45° angles

instead. The shape of the exhaust duct work is not critical so long as the minimum cross section area is

provided.

IMPORTANT: Minimum duct size for a gas dryer and 60 Kw or 72 Kw electric dryer is 14-inches

(35.56 cm) for a round duct or 12-1/2" by 12-1/2" (31.75 cm by 31.75 cm) for a

square duct. The minimum duct size for a steam dryer or 80 Kw electric dryer is

16-inches (40.64 cm) for a round duct or 14-1/2" by 14-1/2" (36.83 cm by

36.83 cm) for a square duct. DUCT SIZE MUST NOT BE REDUCED

ANYWHERE DOWN STREAM OF THE DRYER.

IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust

duct area should not exceed 0.3 inches of water column (0.74 millibars).