Accessories, Installing the unit (only for ex- perts), Ec declaration of conformity – Karcher Système de recyclage des eaux usées WRP 16000 User Manual
Page 22
-
10
Order No. 6.272-001.0 (Grain size 04,...0.8
mm) in 25 kg sack
Order No. 6.272-003.0 (Grain size 1...2
mm) in 25 kg sack
Needed for one fiter filling
Notice
The equipment may only be installed by an
–
mechanic of Kärcher
–
or an from Kärcher authorized individu-
al
The following requirements are necessary
in order to install the equipment:
–
frost-free room with adequate ventila-
tion and exhausts
–
Floor path for collecting sludge
–
Pipes and underground construction as
per drawings 0.089-491.0 and 0.089-
492.0.
–
Water and electrical connection: see
"Technical data"
–
horizontal, even foundation
–
Protect the plant against direct sunlight
and spray water
–
Sufficiently illuminate the installation
site
–
The floor must be freely accessible.
Unpack the equpiment and dispose of the
packing material properly.
The water installation depends on the spe-
cific conditions of the existing plant compo-
nents such as
–
Type and model of washing unit
–
Type and models of building-side com-
ponents (sludge collector, pump basin,
etc.)
–
Nominal widtht, lengths and type of
channels
Hence, the water installation must be car-
ried out according to the specific project
documents.
ƽ
Danger
Risk of injury on account of tripping and fall-
ing.
Lay the hoses of the plant in such a way
that they do not pose a risk for tripping and
falling.
ƽ
Danger
Risk of electrical voltage. All electrical in-
stallations may only be done by an electri-
cian according to the local regulations.
The plant must be secured through a wrong
current protection switch with a triggering
current lesser than or equal to 30 mA.
–
The appliance may only be connected
to alternating current.
–
The appliance may only be connected
to an electrical supply which has been
installed by an electrician in accord-
ance with IEC 60364.
–
The voltage indicated on the type plate
must correspond to the voltage of the
electrical source.
We hereby declare that the machine de-
scribed below complies with the relevant
basic safety and health requirements of the
EU Directives, both in its basic design and
construction as well as in the version put
into circulation by us. This declaration shall
cease to be valid if the machine is modified
without our prior approval.
The undersigned act on behalf and under
the power of attorney of the company man-
agement.
Authorised Documentation Representative
S. Reiser
Alfred Kärcher GmbH Co. KG
Alfred-Kärcher-Str. 28 - 40
71364 Winnenden (Germany)
Phone: +49 7195 14-0
Fax: +49 7195 14-2212
Winnenden, 2014/01/01
Accessories
Filter gravel, fine
Filter gravel, medium
Filter gravel,
fine 6.272.-
001.0
Filter gravel,
medium 6.272.-
003.0
WRP
8000
7 sacks
2 sacks
WRP
16000
10 sacks
3 sacks
Accessories
Order number
Recycled water tank
2.642-720.0
Additional tank
2.642-930.0
Upgrade kit tank con-
nection, 2 tanks
4.640-401.0
Upgrade kit tank con-
nection, 3 tanks
4.640-402.0
Ventilation
2.641-510.0
Overflow
2.641-995.0
Immersion pump
WRP 8000
2.642-037.0
Immersion pump
WRP 16000
2.642-038.0
Stand for switch cabi-
net
2.642-116.0
Conductivity meas-
urement
2.642-765.0
Fresh water supply
WRP 8000
2.642-113.0
Fresh water supply
WRP 16000
2.642-114.0
Installing the unit (only for ex-
perts)
Preparing the installation place
Unpack the equipment
Water installation
Electrical connection
EC Declaration of Conformity
Product:
Water treatment plant
Type:
1.217-xxx
Relevant EU Directives
2006/42/EC (+2009/127/EC)
2004/108/EC
Applied harmonized standards
EN 60204–1
EN 55014–1: 2006+A1: 2009+A2: 2011
EN 55014–2: 1997+A1: 2001+A2: 2008
EN 61000–3–2: 2006+A1: 2009+A2: 2009
EN 61000–3–3: 2008
EN 62233: 2008
CEO
Head of Approbation
22
EN