beautypg.com

Karcher Úpravna vody WPC 5000 CD User Manual

Page 15

background image

English

15

1 Display
2 ADVANCE key

During operations, the current time is
shown in the display.
Î

Press ADVANCE key for 5 to 6 sec-
onds. The display will show the first sta-
tus display from the list shown beloe.

Î

To go to the next display, press once
again the ADVANCE key briefly.

If you do not press the ADVACE key for
some time, the display goes back to show-
ing the time.

The dosing pump must be dearated if the
pump has sucked in air (for e.g. if the dos-
ing container has been completely emp-
tied).
– The unit will stop; the display shows the

interruption "Motor protection".

Note
This errror message is displayed independ-
ent of which dosing container has been
used.

1 Dosing frequency button
2 Screw connections
3 Dosing pump

Î

Refill dosing station (refer chapter on
Startup)

Î

Loosen screws on the dosing pump.

Î

Read and note the dosing frequency
that has been set at the LEDs of the
dosing pump.

Î

Set the dosing frequency to 100% by re-
peatedly pressing the dosing frequency
button and waiting until there are no
more bubbles in the suction pipe (ap-
prox. 1 minute). Absorb the oozing dos-
ing liquid with a piece of cloth.

Î

Tighten the screws.

Î

Set the dosing pump to the original dos-
ing frequency.

1 Return key

Î

Accept the interruption message on the
operating panel by pressing the Return
key; the unit will start.

Î

Check the pressure difference between
the two manometers. Change filter inlay
if value is more that 0.08 MPa (0.8 bar):

Î

Turn the main switch to position "0"

Î

Interrupt raw water inflow.

Î

Open the raw water testing tap to de-
pressurise the filter.

Maintenance schedule

Time

Check / Activity

Target value

In case of deviation

daily

Filling level of dosing container

adequate filling

refill

Air bubbles in the dosing pipes

no air bubbles

Bleed dosing pump.

Drinking water flow based on the startup value Lowered by less than 10%

Fine regulation

Drinking water guide value based on the start-
up value

Increase within 10%

Fine regulation

Pressure difference between pump and con-
centrate pressure

maximum 15% above startup difference

Kärcher Customer
Service

Counter/meter for media and active carbon fil-
ters

Reflushing has taken place in the last 24 hours Kärcher Customer

Service

Pressure difference fine filter

maximum 0.08 MPa (0.8 bar)

Replace fine filter

Visual inspection of the plant

no leaks

Kärcher Customer
Service

weekly

Fill up operations log

monthly

Clean and rinse dosing container

Visual inspection of raw water pump

No damage/ leaks can be detected

Kärcher Customer
Service

Float switch in drinking water tank

no functional disruption can be detected

Kärcher Customer
Service

Maintenance Works

Check media and active carbon filters

Display

Significance

2000

Not important

0000

Not important

D–07

Number of days until the
next reflushing

–001

Number of reflushing that
have been conducted

0–01

days - hours since the last
reflushing

Bleed dosing pump.

Replace fine filter