Instructions for use and maintenance, Troubleshooting – ROTHENBERGER ROREC v.1 User Manual

Page 21

background image

20

INSTRUCTIONS FOR USE AND MAINTENANCE

6. Throttle the Output valve of the unit so that the

output pressure is 100psi greater than the input
pressure, but never more than 300psi.

7. Run until tank is cold

4.5. Tank Cooling Procedure in the recovering process
1. Open the vapor valve of the storage tank (it is

closed while recovering).

2. Close the two valves of the manifold gauge set.
3. Follow the sixth and seventh items of the

Pre-work Cooling Procedure.

4.4. The storage cooling method
Pre-work cooling procedure
1. To start you must have a minimum of 0.5kg of

liquid refrigerant in the tank.

2. Turn the Recover/Purge valve to the Recover

position.

3. Open the Vapor and Liquid valve of the storage

tank.

4. Power on, and start the compressor.
5. Open the Input valve and Output valve of the

unit.

Output

Filter

Liquid

Input

Vapor

Refrigerant
recovery
tank

Input

Liquid

HVAC System

Liquid

Vapor

Vapor

Manifold

gauge set

Refrigerant

recovery

machine

Recovery

tank

Recovery tank

A scale must be used to avoid

overfilling the recovery tank

Filter

Output

PROBLEM

CAUSE

ACTION

Fan does not run
when power Switch is
in “ON” position

Power supply cord not attached Voltage
is not right
The circuit breaker has cut off

Attach the power supply cord.
Check the power supply at job site.
Press the button to reset.

Fan

runs

but

compressor does not
start when the Start
Switch is in “ON”
position

The unit is in high pressure shut off

Output pressure is too high



Failure in motor, or other electrical
components

Reduce pressure and then press the
button of the High Pressure Switch.
Rotate Input valve to “CLOSE”, Purge
valve to “PURGE”, then rotate Input
valve back to “OPEN”, Purge valve to
“RECOVER”.
Factory service required

Compressor starts but
cuts off within a few
minutes

Purge valve is in “PURGE” position
Output valve is not open and high pressure
activates
Recovery tank valve is not open

Rotate Purge valve to “RECOVER”
Rotate Output valve to “OPEN”

Open recovery tank valve

Recovery process too
slow

Head pressure too high

Compressor seals are worn

Reduce

tank

temperature

with

Storage Tank Cooling Method
Factory service required

Unit does not pull out
a vacuum

Connecting hoses are loose
Leakage in unit

Tighten the connecting hoses
Factory service required

5. Troubleshooting