18

Recover

Open

Open

Liquid

Purge

Close

2) If the input valve was throttled back, it

should be fully opened once the liquid has

been removed from the system (the

manifold gauge set vapor port should also

be opened at this time).

9. Run until desired vacuum is achieved.

1) Close the manifold gauge sets vapor and

liquid ports.

2) Turn off the unit.

3) Close the unit’s input port and proceed with

the Self-Purge Method on the next page.

CAUTION: Always purge the unit after each use.

Failure to purge the remaining refrigerant from
the unit could result in the acidic degradation of
internal components, ultimately causing premature
damage.

4.2. Self purging method

Procedure for purging remaining refrigerant
from this unit

1. Turn INPUT valve to CLOSE; OUTPUT valve to

OPEN, and recovery tank valve to OPEN.

2. Turn the Recover/Purge valve to the Purge

position.

3. Check the connection hose, and ensure all

connections are correct and tight. (Same as
recovery mode)

4. Power on and get started.
5. Turn INPUT valve to “PURGE” slowly, and run this

unit until desired vacuum level is achieved or low
pressure protector shuts-off automatically.

6. Close the ports on the recovery tank.
7. Turn the Power-off, disconnect all hoses and dry

the filter.

8. Turn Self-purging to “RECOVER” position, and both

INPUT and OUTPUT valves to “CLOSE” position.

9. Finally, cover the cap on INPUT and OUTPUT

connection adaptor.

INSTRUCTIONS FOR USE AND MAINTENANCE

4. Operation methods

4.1. Standard liquid/vapor recovery method

1. Make sure the unit is in good operating

condition.

2. Make sure all connections are correct and tight.
3. Open the liquid port of the storage tank.
4. Make sure the Recover/Purge valve is set on

Recover.

5. Open the output port of the unit.
6. Open the liquid port on your manifold gauge set;

opening the liquid port will remove the liquid
from the system first. After the liquid has been
removed, open the manifold vapor port to finish
evacuating the system.

Output

Input

Liquid

Manifold

gauge set

HVAC-UNIT/APPLIANCE

CONTAINING REFRIGERANT

Vapor

Filter

Recovery
tank

Liquid

REFRIGERANT

RECOVERY

MACHINE

A scale must be used to avoid

overfilling the recovery tank

Purge

Recover

Open

Open

Liquid

Purge

Close

Purge

Purge

7. Turn “INPUT” valve to “LIQUID” position slowly.
Caution:
--- If the power turns off after starting for some

reason, please try to restart, and if it does not
work, please turn input valve to “CLOSE”. Then
turn the power on again, press “START”to start
the compressor, and turn the INPUT valve to
“LIQUID” slowly.

8. Slowly open the input port on the unit.

1) If the compressor starts to knock, slowly

throttle back the input valve until the

knocking stops.