Location preparation guidelines – ADIC Scalar 1000 User Manual
Page 17

Location Preparation Guidelines
Location Preparation Guidelines
The Scalar 1000 has a series of specifications, rang-
ing from physical to electrical, that vary depending on
the configuration of choice. The following hardware
information relates to all Scalar 1000 configurations,
regardless of the drive technology being used.
Physical Dimensions
Control Module
North America
Europe
Height
6 feet
1.83 m
Width
2 feet 6 inches
0.76 m
Depth
DLT, AIT
3 feet 11 inches
1.19 m
3590
5 feet
1.52 m
Maximum Weight
1
1052 lbs
477 kg
Distributed Load
85 lbs/sq ft
419 kg/sq m
Control Module Physical Dimensions
Expansion Module
North America
Europe
Height
6 feet
1.8 m
Width
2 feet 6 inches
0.76 m
Depth
DLT, AIT
3 feet 11 inches
1.19 m
3590
5 feet
1.52 m
Maximum Weight
1
817 lbs
372 kg
Distributed Load
66 lbs/sq ft
326 kg/sq m
Expansion Module Physical Dimensions
Shipping Requirements
When crated for shipping and delivery, the Scalar
1000 needs a certain amount of space to clear building
openings. Shipped product dimensions are identified
below so customer sites can determine, in advance, the
ideal delivery location and proper door openings.
Control or Expansion
Module
North America
Europe
Height
6 feet 6 inches
1.98 m
Width
2 feet 11 inches
0.9 m
Depth
DLT, AIT
5 feet 5 inches
1.65 m
3590
6 feet 6 inches
1.98 m
Maximum Weight
1100 lbs
499 kg
1
Includes the weight of (12) DLT 7000 tape drives
or equivalently (4) IBM 3590 drives.
fifteen