SI-111 Precision Infrared Radiometer


9: Z=X+F (P34)
1: 8

X Loc [ SB_Temp_K ]

2: -273.15 F
3: 9

Z Loc [ SB_Temp_C ]


;Instruction to measure the mV output of the thermopile.

10: Volt (Diff) (P2)
1: 1

Reps

2: 21

2.5 mV 60 Hz Rejection Range

3: 2

DIFF

Channel

4: 11

Loc

[

mV_tpile

]

5: 1.0

Mult

6: 0.0

Offset


;Calculation of m (slope) coefficient for target temperature calculation. Each sensor has unique

;C0, C1, and C2 values. Refer to the calibration sheet shipped with the sensor to obtain the correct

;values for your sensor.

11: Polynomial (P55)

1: 1

Reps

2: 9

X Loc [ SB_Temp_C ]

3: 12

F(X) Loc [ m_slope ]

4: 15182.65 C0

5: 86.85177 C1

6: 0.69817 C2

7: 0.0

C3

8: 0.0

C4

9: 0.0

C5

12: Z=X*F (P37)

1: 12

X Loc [ m_slope ]

2: 99999 F

3: 12

Z Loc [ m_slope ]

;Calculation of b (intercept) coefficient for target calculation. Each sensor has unique C0, C1, and

;C2 values. Refer to the calibration sheet shipped with the sensor to obtain the correct values for

;your sensor.

13: Polynomial (P55)

1: 1

Reps

2: 9

X Loc [ SB_Temp_C ]

3: 13

F(X) Loc [ b_inter ]

4: -31.09271 C0

5: -2.95714 C1

6: 0.25154 C2

7: 0.0

C3

8: 0.0

C4

9: 0.0

C5

14: Z=X*F (P37)

1: 13

X

Loc

[

b_inter

]

2: 99999 F

3: 13

Z Loc [ b_inter ]

7