beautypg.com

3 troubleshooting, 5 cr1000 keyboard/display, 1 general description – Campbell Scientific RAWS-P Remote Automated Weather Station User Manual

Page 26: Troubleshooting, Cr1000 keyboard/display, General description, 3. cr1000, Keyboard/display

background image

RAWS-P Remote Automated Weather Station

5.4.3 Troubleshooting

If a problem is suspected, the TX320 may be checked by measuring the +12 V
and Ground terminal on the CR1000 PC-board wiring panel. Acceptable
readings are +11 to +14 Vdc. Check the SC12 cable connection between the
CR1000 wiring panel and the TX320. Press the TX320 diagnostic button to
query the state of the transmitter. If problems persist, try a substitute. Obtain
an RMA number before returning this equipment to Campbell Scientific for
repair.

Consult the TX320 manual for more information.

NOTE

5.5 CR1000 Keyboard/Display

5.5.1 General Description

The CR1000 Keyboard/Display (pn CR1000KD) shown in FIGURE 5-3 is
used to check datalogger status, to display or plot sensor readings and stored
values, to enter numeric data, or to change port/flag state. The CR1000KD is
powered from the CR1000 printed circuit board “CS I/O” connector via a
standard 9-pin serial cable (pn 10873) that ships with the RAWS.

Use the CR1000KD menus to enter GOES DCP-Setup
Parameters and to select the wind speed/direction sensor on the
RAWS.

NOTE

FIGURE 5-3. CR1000 keyboard/display

18