5.4.3 Troubleshooting
If a problem is suspected, the TX320 may be checked by measuring the +12 V
and Ground terminal on the CR1000 PC-board wiring panel. Acceptable
readings are +11 to +14 Vdc. Check the SC12 cable connection between the
CR1000 wiring panel and the TX320. Press the TX320 diagnostic button to
query the state of the transmitter. If problems persist, try a substitute. Obtain
an RMA number before returning this equipment to Campbell Scientific for
repair.
Consult the TX320 manual for more information.