AM416 RELAY MULTIPLEXER

9

FIGURE 7. Wiring Diagram for Strain Gages and Potentiometers

(8) Additional Loops - Additional loops may be
used if sensors that require different
measurement instructions are connected to the
same multiplexer. In this instance, like sensors
are assigned to sequential input SETS. Each
group of sensors is measured in a separate
loop (steps 2 through 7, Figure 4). Each loop
contains clock and measurement instructions,
and all loops must reside between the
instructions that activate and deactivate the
AM416 (Steps 1 and 9).

The instruction sequence for control of an
AM416 is given on the following page. The
Program format is a product of EDLOG, a
datalogger program editor contained in CSI's
PC208 Datalogger Support Software.

5.2 MULTIPLE LOOP INSTRUCTION SEQUENCE

As shown above, the program for operation of
the AM416 is essentially the same for all CSI
dataloggers. To measure sensors of different
types, different measurement instructions may
be used within successive program loops. In
the following example, each loop is terminated
with Instruction 95, and the multiplexer is not
reset between loops. The following example
demonstrates measurement of two dissimilar
sensor types (i.e. strain gages and
potentiometers).

The program and accompanying wiring diagram
are intended as examples only; users will find it
necessary to modify both for specific
applications.

*

1

Table 1 Programs

01:

60

Sec. Execution Interval

ENABLES MULTIPLEXER
01:

P20

Set Port

01:

1

Set high

02:

1

Port Number

BEGINS STRAIN GAGE MEASUREMENT LOOP
02:

P87

Beginning of Loop

01:

0

Delay

02:

10

Loop Count

CLOCK PULSE
03:

P22

Excitation with Delay

01:

1

EX Chan

02:

1

Delay w/EX (units=.01sec)

03:

1

Delay after EX (units=.01sec)

04: 5000

mV Excitation

FULL BRIDGE MEASUREMENT INSTRUCTION
04:

P6

Full Bridge

01:

1

Rep

02:

3

50 mV slow Range

03:

1

IN Chan

04:

2

Excite all reps w/EXchan 2

05: 5000

mV Excitation

06:

1--

Loc [:STRAIN #1]

07:

1

Mult

08:

0

Offset

END OF STRAIN GAGE MEASUREMENT LOOP
05:

P95

End