52202 Electrically Heated Rain and Snow Gage

5.2.2 CR10X Example Program

;{CR10X}
;
*Table 1 Program
01: 1

Execution

Interval

(seconds)


1: Pulse (P3)
1: 1

Reps

2: 8

Control Port 8 (switch closure only) ;Black wire connect to C8

3: 2

Switch Closure, All Counts

4: 1

Loc

[

Rain_mm

]

5. 0.1

Multiplier

6: 0

Offset


2: If time is (P92)
1: 0

Minutes (Seconds --) into a

2: 60

Interval (same units as above)

3: 10

Set Output Flag High (Flag 0)


3: Set Active Storage Area (P80)
1: 1

Final Storage Area 1

2: 101

Array

ID


4: Real Time (P77)
1: 1220

Year,Day,Hour/Minute

(midnight

=

2400)


5: Totalize (P72)
1: 1

Reps

2: 1

Loc

[

Rain_mm

]


*Table 2 Program
02: 0.0000 Execution

Interval

(seconds)


*Table 3 Subroutines

End Program

Output Instruction 72, Totalize, is used in the output section of the program to
output the total rainfall over the output interval. This section should be
executed every scan and not placed in a subroutine or conditional statement.

6. Troubleshooting

6.1 Precipitation

Symptom: No Precipitation

1. Check that the sensor is wired to the pulse channel or control port

specified by the pulse count instruction.

2. Verify that the Configuration Code (Switch Closure), and Multiplier and

Offset parameters for the Pulse Count instruction are correct for the
datalogger type.