beautypg.com

Installation, 1 wiring to datalogger, 2 datalogger programming – Campbell Scientific 109SS Temperature Probe User Manual

Page 12: Wiring to datalogger, Datalogger programming, 1. wire color, function, and datalogger connection

background image

Model 109SS Temperature Probe

Stainless-Steel Sheath

Diameter: 0.16 cm (0.063 in)

Length:

5.84 cm (2.3 in)

Overmolded Joint

Diameter: 1.02 cm (0.40 in)

Length:

4.24 cm (1.67 in)

Cable:

Santoprene

®

, 0.220 in diameter

Cable/Probe Connection:

ATUM

TM

heat shrink

Macromelt

®

overmolded joint

Weight:

0.2 lb per 10.5 ft cable

7. Installation

If you are programming your datalogger with Short Cut, skip Section 7.1,

Wiring to Datalogger, and Section 7.2, Datalogger Programming. Short Cut

does this work for you. See Section 4, Quickstart, for a Short Cut tutorial.

7.1 Wiring to Datalogger

TABLE 7-1. Wire Color, Function, and Datalogger Connection

Wire Color

Wire Function

Datalogger Connection

Terminal

Black

Voltage-excitation input

EX, VX

(voltage excitation)

Red

Analog-voltage output

SE

(single-ended,

analog-voltage input)

Purple

Bridge-resistor lead

AG or

(analog ground)

Clear

EMF shield

G

(power ground)

7.2 Datalogger Programming

Short Cut is the best source for up-to-date datalogger programming code.

Programming code is needed when:

Creating a program for a new datalogger installation.

Adding sensors to an existing datalogger program.

If your data acquisition requirements are simple, you can probably create and

maintain a datalogger program exclusively with Short Cut. If your data

acquisition needs are more complex, the files that Short Cut creates are a great

source for programming code to start a new program or add to an existing

custom program.