B attery to inverter cable connection – Samlex America ST1500-148 User Manual
Page 18

17
3-3-1. Connect the cables to the power input terminals on the front panel of the
inverter. The red terminal is positive (+) and black terminal is negative (-).
Insert the cables into the terminals and tighten screw to clamp the wires
securely.
Also, only use high quality copper wire and keep the cable length short
which is a maximum of 3 - 6 feet.
D o not place anything betw een
battery cable lug and term inal surface.
A ssem ble exactly as show n.
A W G # 2 - #6
B attery to inverter cable connection
WARNING!
The installation of a fuse must be on positive cable.
Failure to place a fuse on “+” cables running between
the inverter and battery may cause damage to the
inverter and will void warranty.
WARNING!
Make sure all the DC connections are tight (torque
to 9 – 10 ft-lbs, 11.7 – 13 Nm). Loose connections
could result overheat in a potential hazard.