Siemens LI48932 User Manual
Page 17
17
Before installation
Optimum efficiency of the extractor
hood:
❑ Short, smooth exhaust pipe.
❑ As few bends as possible.
❑ Pipe diameter as large as possible
(ideally 150 mm dia.) and wide pipe
bends.
If long, rough exhaust-air pipes,
many pipe bends or smaller pipe
diameters are used, the air extraction
rate will no longer be at an optimum
level and there will be an increase in
noise.
ṇ
The manufacturer of the
extractor hoods accepts no liability
for complaints which can be
attributed to the design and layout of
the pipework.
❑ Round pipes
Short exhaust air pipe:
inside diameter
min. 120 mm,
Longer exhaust air pipe:
inside diameter
min. 150 mm.
❑ Flat ducts must have an inside
cross-section equivalent to that of the
round pipes.
There should be no sharp bends.
l
120 mm dia. approx. 113 cm
2
l
150 mm dia. approx. 177 cm
2
❑ If pipe diameters differ, insert sealing
strip.
❑ Ensure that there is an adequate air
supply for
exhaust air mode.
Exhaust air directed backwards:
Only possible inside tall wall cupboards
depending on the size of the exhaust air
pipe.
❑ Make a hole in the rear panel of the wall
cupboard, cutting out a notch for the
power supply cable.
Exhaust air directed upwards:
Circulating-air mode
❑ With activated carbon filter if exhaust-air
mode is not possible.
ṇ
The complete
installation set can be
obtained
from specialist
outlets.
The corresponding
accessory numbers can
be found at the end of
these operating instructions.
1. Make a hole in the top of the wall cupbo-
ard, cutting out a notch for the power
supply cable.
– template
O
I
enclosed –.
2. If fitted, cut out the cupboard base to a
min. depth of 270 mm over the entire
width.
Note:
❑ An installation kit is required if the width
of the cupboard is 900 mm.
Connecting a 150 mm exhaust pipe:
❑ Attach the exhaust pipe directly to the air
connector.
Connection of 120 mm l exhaust air
pipe:
❑ Attach enclosed reducing connector to
the air outlet.
Holes in the air outlet must be sealed.
❑ Attach exhaust air pipe to the reducing
connector.
Preparing the wall cupboard
This extractor hood is designed to be
installed in a wall cupboard with the follo-
wing dimensions:
width: 600 mm
depth: 293 to 350 mm
height: min. 435 mm.
If the cupboard is deeper than 293 mm,
the extractor hood can be moved back,
e.g. to put a spice rack in front of the
extractor hood.
To do this, place the template
O
II
further
back.
ṇ
Ensure that the cupboard is stable
both during and after installation, even if
fitted at the end of a row of kitchen units.
ṇ
Do not install the extractor hood at the
end of the kitchen line.
ṇ
Align the cupboards exactly. If requi-
red, place the side cupboards flush under-
neath.
ṇ
The side panels must not project over
the base of the adjacent unit by more than
Exhaust air
Circulating air
16,0
16,5
We reserve the right to construction changes within the
context of technical development.
Weight in kg: