beautypg.com

Z s z s, Z” and “s” pots – Ashcroft A4 - Pressure Transmitter User Manual

Page 4

background image

Power Supply

Power Supply Voltage

Output Signal

Min

Max

4-20mA*

12V**

30V

* Refer to Ashcroft drawing #825A022 for

supply voltage and load limit.

** The minimum voltage at the terminals is

12Vdc. However, the minimum supply
voltage should be calculated using the
following graph and formula.

A4 INTRINSICALLY SAFE &
NON-INCENDIVE RATED
PRESSURE TRANSMITTER
INSTRUCTION SHEET

Mounting

The A4 transmitter requires no special

mounting hardware, and can be mounted
in any plane with negligible position error.

Although the unit can withstand normal

vibration without damage or significant
output effects, it is always good practice
to mount the transducer where there is
minimum vibration.

For units with NPT type pressure fittings

apply Teflon

®

tape or an equivalent

sealant to the threads before installing.

When tightening, apply a wrench to the

hex wrench flats located just above the
pressure fitting. DO NOT tighten by using
a pipe wrench on the housing.

Noise
For minimum noise susceptibility, avoid
running the transducer’s cable in a con-
duit that contains high current AC power
cables. Where possible avoid running
the cable near inductive equipment.

Shielded Cable
Units with shielded cable electrical termi-
nation, connect the drain wire to the
guard terminal on the read out device or
measuring instrument, if available. In all
other cases connect to the ground or to
the power supply negative terminal.

Vent Tube (Cable Termination Only)
The cable has a clear Teflon

®

vent tube

required at pressure ranges below 500
psi to provide atmospheric reference.
The open end should be placed in a
dry area.

+

+

POWER
SUPPLY

(+)

(–)

TRANSDUCER

V+

V–

PIN 1

PIN 2

4-20mA

METER

OR OTHER DEVICE

A4 Wiring Diagrams

Zero and Span Adjustment
Instructions below apply to the particular
configurations noted. While Zero adjust-
ment is not normally necessary, it may be
desirable to trim out any offset in the sys-
tem. However, proper Span calibration
requires a pressure standard three to five
times more accurate than the accuracy of
the transducer, and there may also be
interaction of Span on Zero.

A4 transducer has internal transient
protection: for safety, limit line-to-
ground voltage to 36 Vdc max.

© 2011 Ashcroft Inc. All rights reserved. 250 East Main Street, Stratford, CT 06614 USA Tel: 203-378-8281, Fax: 203-385-0402 www.ashcroft.com
All sales subject to standard terms and conditions of sale. I&M011-10166-A4. Rev. 12/12

A4 configurations with enclosure “S”
offer Zero and Span potentiometer
access.
Access to “Z” and “S” pots via the top
(electrical termination end) of the unit is
standard on all “S” enclosure units with 4-
20mA output. Access is gained by remov-
ing the black threaded cap, once removed
you will see the pots indicated by “Z” and
“S” respectively as shown below. Using a
small trim pot tool, you can adjust zero
±10% of full scale and span ±10% of
full scale.

Recalibration Instructions:
1. Apply 0% full scale pressure.
2. Adjust the output using the zero adjust

trim pot.

3. Apply 100% full scale pressure.
4. Adjust the output using the span adjust-

ment trim pot.

5. Repeat steps 1 through 4 as necessary.

.

0

6

2

Z S

Z

S

“Z” and “S” pots

Vmin = 12V+ (.022A x RL) (includes a 10% safety factor)
RL = RS + RW
RL = Loop Resistance (ohms)
RS = Sense Resistance (ohms)
RW = Wire Resistance (ohms)

10

1000

800

600

400

200

0

20

30

Operating

Region

30 Vdc max for
Intrinsically Safe
Installations

Loop Supply Voltage (Vdc)

Loop Supply Voltage vs. Loop Resistance

L

o

o

p

R

e

s

is

ta

n

c

e

(

O

h

m

s

)

HAZARDOUS AREA CERTIFICATIONS

Intrinsically Safe (applies to 4-20mA) FM/CSA:

Intrinsic Safety: Class I, II and III Div.1 and 2,

Groups A, B, C, D, F and G per
entity requirements see Ashcroft
drawing # 825A022

Non-Incendive: Class I, II and III Div.1 and 2,

Groups A, B, C, D, F and G, no
barriers needed