HAZARDOUS (CLASSIFIED) AREA

CLASS I, DIVISION 1 & 2,

GROUPS A, B, C, & D;

CLASS II, DIVISION 1 & 2,

GROUPS E, F & G, CLASS III

NON-HAZARDOUS

(UNCLASSIFIED) AREA

BARRIER

BARRIER

V+

V–

MODEL A2X & A4 SERIES

4-20MA TRANSMITTER

R LOAD

250 OHM

TYP.

R LOAD

250 OHM

TYP.

MODEL A2X & A4 SERIES

4-20MA TRANSMITTER

V+

V–

+24 VDC TYP.

+

–24 VDC TYP.

V OUT

(1-5 V TYP.)

V OUT

(1-5 V TYP.)

4.3 FM INSTALLATION GUIDELINES

NSTALLATION NOTES

Voc OR Vt

≤30VDC

Isc OR It

≤100mA

Ca

≥ 0.053uF + Ccable

La

≥ 0.364uH + Lcable

1. THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTER-

CONNECTION OF TWO INTRINSICALLY SAFE DEVICES FM
APPROVED WITH ENTITY PARAMETERS NOT SPECIFICALLY
EXAMINED IN COMBINATION AS A SYSTEM WHEN: Uo OR Voc
OR V

≤t Vmax, Io OR Isc OR≤ It Imax, Ca OR Co ≥ Ci + Ccable, La

OR

≥Lo Li +Lcable≤, Po Pi.

2. THE NONINCENDIVE FIELD WIRING CONCEPT ALLOWS INTER-

CONNECTION OF NONINCENDING FIELD WIRING APPARATUS
WITH ASSOCIATED NONINCENDIVE FIELD APPARATUS USING
ANY OF THE WIRING METHODS PERMITTED FOR NON3HAZ-
ARDOUS (UNCLASSIFIED) LOCATIONS WHEN: Uo OR Voc OR Vt
Vmax, Io OR Isc OR It Imax, Ca OR Co + Ccable, La OR Lo Li
+Lcable, Po Pi.

3. FOR DIVISION 1 INSTALLATIONS, THE CONFIGURATION OF

ASSOCIATED APPARATUS SHALL BE FM APPROVED UNDER
ENTITY CONCEPT.

4. FOR DIVISION 2 INSTALLATIONS USING NONINCENDIVE FIELD

WIRING CONCEPTS THE ASSOCIATED APPARATUS SHALL BE FM
APPROVED UNDER THE ENTITY CONCEPT OR NONINCENDIVE
FIELD WIRING CONCEPT.

INSTALLATION FOR FM

INTRINSICALLY SAFE CLASS 1, GROUPS A, B, C & D &

CLASS ll, GROUPS E, F & G &

CLASS lll

5. FOR DIVISION 2 INSTALLATIONS THE ASSOCIATED APPARATUS

IS NOT REQUIRED TO BE FM APPROVED UNDER ENTITY CON-
CEPT OR NONINCENDIVE FIELD WIRING CONCEPT IF THE
A2X(4-20mA) & A4 SERIES PRESSURE TRANSDUCER IS
INSTALLED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE (ANSI/NFPA 70) FOR DIVISION 2 WIRING METHODS
EXCLUDING NONINCENDIVE FIELD WIRING.

6. CONTROL EQUIPMENT CONNECTED TO THE ASSOCIATED APPA-

RATUS SHALL NOT USE OR GENERATE MORE THAN 250VRMS
OR VDC.

7. DIVISION 1 INSTALLATIONS SHOULD BE IN ACCORDANCE WITH

ANSI/ISA RP12.06.01, ``INSTALLATION OF INTRINSICALLY SAFE
SYSTEMS FOR HAZARDOUS (CLASSIFIED) LOCATIONS'' AND
THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70).

8. ASSOCIATED APPARATUS MANUFACTURERS INSTALLATION

DRAWING SHALL BE FOLLOWED WHEN INSTALLING THIS
EQUIPMENT.

9. RUN SHIELDED INTERCONNECTION CABLE WITH SHIELD CON-

NECTED TO FM APPROVED ASSOCIATED APPARATUS GROUND.

10. WARNING – DO NOT OPEN WHEN ENERGIZED.

11. WARNING – DO NOT DISCONNECT EQUIPMENT UNLESS AREA IS

KNOWN TO BE NON-HAZARDOUS.