8

7.1.4 Maximum cable length

Depending on the type of illuminator and supply

voltage, comply with the following maximum

distances for the power cables.
Power supply 12Vdc: A 0.6V voltage drop is allowed

on the cables. Minimum voltage of 11.4Vdc at the

power cable input provided with the illuminator.

CABLES SPECIFICATIONS (12VDC POWER SUPPLy)

Cable sec-

tion (mm²)

AWG

Maximum distance (m)

0.75

18

4.5

1

17

6.5

1.5

16

9

2.5

14

15

4

10

24

Tab. 3

Power supply 24Vac: Maximum 3V voltage drop is

allowed on the cable. Minimum voltage of 21Vac at

the power cable input provided with the illuminator.

CABLES SPECIFICATIONS (24VAC/VDC POWER

SUPPLy)

Cable sec-

tion (mm²)

AWG

Maximum distance (m)

0.75

18

35

1

17

50

1.5

16

80

2.5

14

120

4

10

200

Tab. 4

Power supply 90/240Vac: The cable section is less

critical, therefore, it is sufficient to ensure that the

ground connections is efficient for safety reasons.

We recommend using a section of at least 0.75mm²

(AWG18).
Control cable: External command, Colours red and

Green. Follow command, colours White and Black.

Use a minimum section cable of 0,34mm² (AWG22)

and a minimum distance of 200m.

7.1.5 Adjusting the activation threshold

Switch-on threshold

regulation

Infrared illuminators

power setting

Fig. 8

7.1.5.1 Photocell sensitivity

The illuminator has an integrated photocell that

allows its automatic activation and deactivation at

predefined luminous conditions.
The photocell is set in the factory at a predetermined

luminous level, suitable for most installations

(approximately 50Lux). In the event the intervention

threshold (illuminator activation) must be adjusted

differently, loosen the plug on the illuminator rear

and proceed adjusting.