Installation Guide APC BC300 Series 40kW 208/450/480V UPS

990-1401

Installation

3.5.4.4 Triple Chassis Power Considerations
The Triple Chassis receives its power from the UPS through the supplied 24 VDC universal
adapter. The total current required by your management products

must not exceed the 850 mA

limit of the power adapter. See “Determining power requirements”.

3.5.4.5 Determining Power Requirements
To determine the total amount of current required by your management products, add the
individual current requirements for each management product to be installed with the APC
BC300 Triple Chassis to the current requirements of the chassis itself.

3.5.5 Troubleshooting

The following table shows the solutions to common problems with the operation of the Triple
Chassis

3.5.5.1 If Problems Persist
For problems not covered in the troubleshooting chart or for persistent problems, follow this
procedure:

Management Product

Draw (mA)

Share-UPS 8-port Interface Expander

65

Expansion Chassis

30

Triple Chassis

20

APC BC300 Triple Chassis

90

Web/SNMP Management Card

110

Interface Expander

45

Out-of-Band Management Card

35

Environmental Monitoring Card

60

Isolated Extension Cable

50

Remote Power-Off Device

35

Problem

Possible Cause

Solution

Status LED is off

The chassis is not
receiving adequate
power.

See “Powering the APC BC300
Triple Chassis”, and verify that you
are not exceeding current
requirements.

Status LED is flashing
quickly

The chassis has not been
configured.

Configure the Silcon Triple Chassis.
See the Web/SNMP Management
Card Installation Guide on the CD
for more information.

Status LED is flashing
slowly

The chassis is not
communicating with the
UPS.

Verify that the supplied UPS cable is
properly connected to the Triple
Chassis and to a communications
port on the UPS.

Attached management
product cannot identify
UPS model or nominal
output voltage.

The management
firmware does not
support 3-phase UPSs.

You may be able to upgrade the
firmware of the management
product. Call APC Customer
Support.