Installation – APC BC300 Series User Manual

Page 15

background image

Installation

990-1401

Installation Guide APC BC300 Series 40kW 208/450/480V UPS

15

Figure 8 - Single Line Diagram 40kW 450V

Utility Source (provided by others)

450V 3 Wire + Ground

MIB

Service
Bypass
Panel

F4, 5, 6

UIF

Q001

UIS

UPS

F1, 2, 3

UOF

Q002

UOS

Q003

BS

UPS System Output

40kW

450V 3 Wire + Ground

Notes:
1. Must be 3 wire + Ground
2. Must be 3 wire + Ground cabling
provided by others.
3. Input overcurrent protection is based on
80% rating - any deviation, please contact
APC.
4. F1, F2, F3 = 60A
5. F4, F5, F6 = 80A
6. All AC power cabling is 3 wire + Ground
at 208VAC 3-phase.
7. UPS output cables and input cables must
be in separate conduits.
8. Power wiring and control wiring must be
in separate conduits.
9. See installation manual for battery
information.
10. Installation must comply with all
applicable national and local codes.

51A

51A

51A

75A

75A

200A

95AT