Installation Guide APC BC300 Series 40kW 208/450/480V UPS

990-1401

Installation

Figure 2 - SBP Electrical Schematic 208V & 480V

Figure 3 - SBP Electrical Schematic 450V

Notes:
1. 208V F1, F2, F3 = 120A
2. 480V F1, F2, F3 = 55A
3. 208V F4, F5, F6 = 170A
4. 480V F4, F5, F6 = 75A
5. All AC power cabling is 3- or 4-wire + Ground at 208VAC / 480VAC 3-phase.
6. Installation must comply with all applicable national and local codes.

7

3

U

11

15

19

20

16

12

8

4

U

U

U

U

Maintenance

Bypass Switch

Contacts marked "U"

closed in "UPS".

Contacts marked "BP"

closed in Bypass.

Contacts are Make

before Break.

AC Output
from UPS

F1

F2

F3

N

TO CRITICAL

LOAD CENTER

AC Output

to Critical Load

L1

L2

L3

N

G

L1

L2

L3

N

GRD

1

5

13

9

10

14

6

17

18

2

BP

BP

BP

BP

BP

G

G

Uninterruptible
Power Supply

L1

L1

L2

L2

L3

L3

N

N G

AC Input

to UPS

L1

L2

L3

UPS Input

Disc. Switch

Shown in Open

Position

1

2

4

6

5

3

AC Line

Input

F4

F5

F6

L1

L2

L3

N

GRD

Notes:
1. F1, F2, F3 = 60A
2. F4, F5, F6 = 80A
3. All AC power cabling is 3 wire + Ground at 450VAC 3-phase.
4. Installation must comply with all applicable national and local codes.

UPS Maintenance

Bypass Switch

UPS Bypass

1

3

5

7

9

11

13

15

17

19

1

3

5

7

2

4

6

8

10

12

14

16

18

20

2

4

6

8

BYP

UPS

BYP

BYP

BYP

BYP

UPS

UPS

UPS

UPS

UPS

BYP

BYP

BYP

1

3

5

2

4

6

UPS Input

Disconnect

Switch

On-Off

Relay

R

14

13

1

9

"UPS in Static Bypass" Ind. Light

"UPS in Maintenance Bypass" Ind. Light

R

G

Keyed Solenoid Lock Release Switch

Lock

Release

0X

0X

X0

X0

13

22

31

43

14

21

32

44

Solenoid Lock

Mechanism

(Energize to Unlock)

N

120 VAC

X

+

-

120 VDC

5A

440, 450, 480

VAC Primary

440, 450, 480

VAC Primary

120 VAC

Secondary

XFMR 1

120 VAC

Secondary

XFMR 2

H1

H3

H2

H4

H1

H3

H2

H4

X1

X1

X2

X2

F1A

1A

1

2

3

4

5

6

C

N

N

D

C

Auxiliary Switch Circuit

G

L1

L2

L3

AC Input to UPS

F4-F5-F6

F1-F2-F3

G

L1

L2

L3

AC Line Input

G

L1

L2

L3

G

L1

L2

L3

AC Output from UPS

AC Output

to Critical Load