Closed-loop Valve Controller
Parameter List
The following table outlines the DRF parameters as well as the limits and units of measure for each parameter.
Parameter
Limits
Units
DRFx-xxx
Version #
C1 Mode
See Mode Description
Mode #
C1 Proportional gain
0.0 to 100
%
C1 Integral gain
0.0 to 100
%
C1 Derivative gain
0.0 to 100
%
C1 PID loop time
1 to 30
Cycles
C1 Deadband
0.0 to 2.0
V (mA)
Previous 5 parameters repeated for channel 3
2
C1 Min input
-10 to +10.0; 4 to 20.0
V (mA)
C1 Max input
-10 to +10.0; 4 to 20.0
V (mA)
C1 Min output
0 to 600
1
mA
C1 Max output
0 to 600
1
mA
C1 Ramp up
0.0 to 120.0
Seconds
C1 Ramp down
0.0 to 120.0
Seconds
Previous 6 parameters repeated for all channels
2
Dither frequency
30 to 1000
Hz.
C1 Command input
V (mA)
C1 Output current
mA
Previous 2 parameters repeated for all channels
2
Supply voltage
Volts
Fault status
Fault
1
0 to 1.2 A for
–12A version, 0 to 2.5 A for –25A version
2
Parameters starting with C1 are repeated for each channel and are displayed as C2 to C4