Operating and installation instructions
Liquid return temperature limiter
7.3 Tightening torques
(refer to Fig. 1 page 4 - Fig. 4 page 8)
8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 Troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting table
Pos.
Liquid return temperature
limiter PN25/40
Torque (Nm)
6
Screw cap
100
24
Controller
80
43
Plug 70
47
Thermometer adapter
50
48
Thermometer
50
-
ATTENTION !
- It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Installed in wrong flow direction.
Fit valve in direction of flow arrow.
Note installation position
Flange covers not removed
Remove flange covers
Little flow
Piping system clogged
Check piping system
Changed upstream pressure or back
pressure operating conditions
Correct selection according to flow
diagram
No closure, or internal
leakage
Controller clogged
Clean controller; refer to item 7.1
Controller worn out
Change controller; refer to item 7.1
Controller shifted / misadjustedt
Check adjustment; refer to item 5.3
Controller incorrectly screwed into body Check seal face between body and con-
troller, tighten controller correctly;
refer to item 7.3
Controller operated above safe operating
pressure
Observe operating limits as per data
sheet
External leakage
Screw cap (Pos. 6) not properly
tightened
Tighten; refer to item 7.3
Plug (Pos. 43) not properly tightened
Tighten; refer to item 7.3