0 troubleshooting, 0 troubleshooting table, Operating and installation instructions codi – ARI Armaturen CODI B PN63 EN User Manual
Page 11: 5 tightening torques
![background image](/manuals/409392/11/background.png)
Rev. 0040807006 1404
Page 11
Operating and installation instructions
CODI
®
S/B -
Condensate collection / steam distribution
7.5 Tightening torques
(refer to Fig. 2 page 5 - Fig. 5 page 9)
8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting table
Pos.
CODI S / B
Torque (Nm)
6
Sleeve nut
10
12
Threaded bush
10
13
Safety nut
70
14
Banjo bolt
70
15
Fitting
90
16
Stem guiding
90
-
ATTENTION !
It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Installed in wrong flow direction.
Fit valve in direction of flow arrow
Flange covers not removed
Remove flange covers
Little flow
Piping system clogged
Check piping system
No closure, or internal
leakage
Shut-off valve clogged
Clean shut-off valve; refer to item 7.1
Shut-off valve worn
Replace shut-off valve; refer to item 7.1
Shot-off valve operated above safe oper-
ating pressure
Observe operating limits as per data
sheet
External leakage
Shut-off valve not properly tightened
Tighten; see 7.5
Seal (Pos. 5, 10) defective
Replace sealing;
refer to item 7.2 and 7.3