beautypg.com

0 troubleshooting, 0 troubleshooting table, Operating and installation instructions cona – ARI Armaturen CONA S PN40 EN User Manual

Page 10: S - ball float steam traps

background image

Page 2-10

Rev. 0040805005 3614

Operating and installation instructions

CONA

®

S - Ball float steam traps

8.0 Troubleshooting

In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.

If malfunctions cannot be eliminate with the help of the following table
9.0 troubleshooting table”, the supplier or manufacturer should be consulted.

9.0 Troubleshooting table

-

ATTENTION !
It is essential that the safety regulations are observed when identifying faults.

ATTENTION !
- refer to item 10.0 and 11.0 prio
r to dismantling and repair work!
- refer to item 6.0 befo
re restarting the plant !

Fault

Possible cause

Corrective measures

No flow

Installed in wrong flow direction.

Fit valve in direction of flow arrow.
Note installation position;
refer to item 5.4!

Flange covers not removed

Remove flange covers

Ball float (Pos. 24.16) defective

Check lifting force; refer to item 7.1

Little flow

Piping system clogged

Check piping system

Wrong controller size choosen

Correct selection acc. to flow diagram

Changed upstream pressure or back
pressure conditions

Correct selection acc. to flow diagram

No closure, or internal
leakage

Controller clogged

Clean controller; refer to item 7.1

Controller or diaphragm capsule clogged Clean controller and/or diaphragm

capsule; refer to item 7.1

Controller worn out

Change controller; refer to item 7.1

Controller or diaphragm capsule worn
out

Change controller and/or diaphragm
capsule; refer to item 7.1

Controller incorrectly screwed into body Check seal face between body and

controller, tighten controller correctly;
refer to item 7.3

Controller operated above safe operating
pressure

Observe operating limits as per data
sheet, i.e. possibly select different
controller

External leakage

Cover (Pos. 40) not properly tightened
with hex. nut (Pos. 28)

Tighten; refer to item 7.3

Flat gasket (Pos. 17) defective.

Replace sealing;
refer to item 7.1

This manual is related to the following products: