0 troubleshooting, 0 troubleshooting table, Operating and installation instructions cona – ARI Armaturen CONA S PN40 EN User Manual
Page 10: S - ball float steam traps
![background image](/manuals/409390/10/background.png)
Page 2-10
Rev. 0040805005 3614
Operating and installation instructions
CONA
®
S - Ball float steam traps
8.0 Troubleshooting
In the event of malfunction or faulty operating performance check that the installation and
adjustment work has been carried out and completed in accordance with these Operating
Instructions.
If malfunctions cannot be eliminate with the help of the following table
“9.0 troubleshooting table”, the supplier or manufacturer should be consulted.
9.0 Troubleshooting table
-
ATTENTION !
It is essential that the safety regulations are observed when identifying faults.
ATTENTION !
- refer to item 10.0 and 11.0 prior to dismantling and repair work!
- refer to item 6.0 before restarting the plant !
Fault
Possible cause
Corrective measures
No flow
Installed in wrong flow direction.
Fit valve in direction of flow arrow.
Note installation position;
refer to item 5.4!
Flange covers not removed
Remove flange covers
Ball float (Pos. 24.16) defective
Check lifting force; refer to item 7.1
Little flow
Piping system clogged
Check piping system
Wrong controller size choosen
Correct selection acc. to flow diagram
Changed upstream pressure or back
pressure conditions
Correct selection acc. to flow diagram
No closure, or internal
leakage
Controller clogged
Clean controller; refer to item 7.1
Controller or diaphragm capsule clogged Clean controller and/or diaphragm
capsule; refer to item 7.1
Controller worn out
Change controller; refer to item 7.1
Controller or diaphragm capsule worn
out
Change controller and/or diaphragm
capsule; refer to item 7.1
Controller incorrectly screwed into body Check seal face between body and
controller, tighten controller correctly;
refer to item 7.3
Controller operated above safe operating
pressure
Observe operating limits as per data
sheet, i.e. possibly select different
controller
External leakage
Cover (Pos. 40) not properly tightened
with hex. nut (Pos. 28)
Tighten; refer to item 7.3
Flat gasket (Pos. 17) defective.
Replace sealing;
refer to item 7.1