0 troubleshooting table, 0 troubleshooting table -15, Bbd 415 – ARI Armaturen STEVI BBD 415 DN 25-50 EN User Manual
Page 15

Rev. 0040321000 0714
Page 2-15
Operating and Installation Instructions
Straight-through blow-down valves - STEVI
®
BBD 415
9.0 Troubleshooting table
ATTENTION !
- Read sections 10.0 and 11.0 prior to all dismantling or repair work!
- Read section 6.0 before restarting the plant!
Fault
Possible cause
Corrective measure
No flow
Valve closed.
Open valve (using actuator).
Flange covers not removed.
Remove flange covers.
Little flow
Valve not sufficiently open.
Open valve (using actuator).
Piping system clogged.
Check piping system.
Valve stem moves in jerks Stuffing box seal too tight (valves with
graphite packing).
Slacken screw joint (pos. 29) slightly;
valve must not begin to leak.
Valve stem leaking
PTFE V-ring unit damaged or worn.
Replace seal pack (pos. 12);
refer to section 7.1.1.
Screw joint (pos. 29) is not tight (valves
with stuffing box packing).
Tighten screw joint (pos. 29) and
replace packing if necessary.
Leakage too high when
valve closed
Sealing surfaces of plug eroded or
worn.
Replace plug;
refer to section 7.2.
Sealing edge of seating damaged or
worn.
Grind seat.
Seating and/or plug dirty.
Clean valve trim.
Pneumatic actuator not completely
vented; spring force not fully effective.
Vent actuator air chamber completely.
Actuator not powerful enough.
Install more powerful actuator.
Actuator unit does not
move
No compressed air on control pressure
line.
Identify causes and take remedial
action.
Actuator unit incorrectly installed.
Check actuator mode of operation and
connect to control pressure line
accordingly.
Rolling diaphragm defective.
Replace rolling diaphragm and springs.
Not enough positioning
force
Stem seal is leaking.
Replace stem seal.
Vent is clogged and air cannot escape
from actuator.
Screw plug must be unclogged.
Actuator not completely vented.
Check controller adjustment.