SERIAL SET-UP DIP SWITCH OPERATION

Serial port configuration is accomplished through two banks of DIP switches

on the

MODBUS

card. The bank of 8 switches sets the Unit Address, the bank

of 7 switches sets the Serial port parameters (ASCII/RTU, 7/8 bits, Parity, and
Baud rate). Changes to the switch settings are only detected on power-up of the
unit. After changing a switch setting, power to the unit must be cycled for the
new switch setting to take effect.

Both unit address and serial set-up are set via DIP switches on the

MODBUS

option card. See the DIP switch setting table for more details on these
DIP switches.

For the Unit Address bank, the high order bit is switch 1, and the ON

position is a ‘1’, the OFF position is a ‘0’. Legal unit addresses are 1 to 247.
When a Unit Address of 0 is selected, the card responds to Unit Address 1.
When a Unit Address of 248 through 255 is selected, the card responds to Unit
Address 247.

For the serial bank, the following settings apply:

BAUD RATE SWITCH SELECTIONS

SWITCH

SETTINGS AVAILABLE

RTU

1

OFF: ASCII

ON: RTU

8 Bits

2

OFF: 7 Bits

ON: 8 Bits

No Parity

3

OFF: None

ON: Parity

OFF

4

OFF: Even

ON: Odd

5

Baud Rate

9600

6

Baud Rate

(See Baud Rate
Switch Selections)

7

Baud Rate

5

6

7

38400:

ON

ON

ON

19200:

ON

ON

OFF

9600:

ON

OFF

ON

4800:

ON

OFF

OFF

2400:

OFF

ON

ON

1200:

OFF

ON

OFF

600:

OFF

OFF

ON

300:

OFF

OFF

OFF

SERIAL SET-UP

UNIT ADDRESS

ON

1 2 3 4 5 6 7 8 1 2 3 4 5 6 7

BIT

WEIGHT

S

(+128)

(+64)

(+32)

(+16)

(+8)

(+4)

(+2)

(+1)

FACTORY

SETTINGS

12

12

B(

-

)

33K

33K

33K

33K

+5V

+5V

Transmit

Transmit

Enable

Enable

PAX METER

PAX METER

RECEIVING DEVICE

RECEIVING DEVICE

A(+)

(+)

COMM.

COMM.

*

NC

NC

* OPTIONAL

OPTIONAL

13

13

14

14

15

15

Terminal Block Connection Figure

3

5

4

2

PAX CONNECTOR

Not used

Not used

Not used

B-

A+

COMM

Extended Comms Connection Figure

RS485 COMMUNICATIONS

The RS485 communication standard allows the connection of up to 32

devices on a single pair of wires, distances up to 4,000 ft. and data rates as high
as 10M baud (the PAX is limited to 19.2k baud). The same pair of wires is used
to both transmit and receive data. RS485 is therefore always half-duplex, that
is, data cannot be received and transmitted simultaneously.