beautypg.com

Red Lion ICM4 User Manual

Description, Safety summary, Specifications

background image

1

z

ALLOWS COMMUNICATIONS BETWEEN RS232 CONTROL

EQUIPMENT AND PRODUCTS WITH RS485 SERIAL
COMMUNICATIONS

z

WIDE DC INPUT POWER RANGE (+9 to 32 VDC)

z

HALF DUPLEX (RS485) AND FULL DUPLEX (RS422)

z

LED INDICATION FOR RXD, TXD, and POWER

z

UNIVERSAL MOUNTING FOOT FOR DIN RAIL INSTALLATION

DESCRIPTION

The ICM4 Serial Converter Module provides the capability of interfacing

equipment with RS485 serial communications to equipment with RS232
communications. Data format of the RS232 and RS485 equipment must be
the same.

For full duplex (RS422), the DIP switch on the side of the module must be in

the RS422 position. For half duplex (RS485), the DIP switch must be in the
RS485 position. In half duplex mode, the RS485 driver is enabled using the
leading edge of the first character transmitted (RXD input). After the last
character transmits, the converter waits one character time (at 9600 baud) to
disable the RS485 driver.

There are 3 LED’s that can be viewed from the front of the converter module.

A green power LED indicates power is on, a red RS232 TXD LED flashes when
the module is transmitting, and a green RS232 RXD LED flashes when the
module is receiving.

An external DC power source (+9 to 32 VDC) is required to power the ICM4.

The external power source and serial communications connections are made via
a 12 position removable terminal block located on the front of the module.

The unit is equipped with a universal mounting foot for attachment to

standard DIN style mounting rails, including top hat profile rail according to
EN50022 - 35 x 7.5 and 35 x 15, and G profile rail according to EN50035 - G32.

SAFETY SUMMARY

All safety related regulations, local codes and instructions that appear in the

manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.

SPECIFICATIONS

1. POWER: +9 to 32 VDC @ 75 mA maximum. Above 26 VDC, derate max.

operating temperature to 40°C. Power supply must be Class 2 or SELV rated.

2. RS232 VOLTAGES:

Receive Data Pin:

±

30 VDC max.

Mark Condition:

0.8 VDC

Space Condition:

2.4 VDC

Transmit Data Pin:

Mark Condition:

8 VDC (typ.)

Space Condition:

+

8 VDC (typ.)

3. RS485 VOLTAGES:

Differential Output Voltage:

±

5 VDC max. under no load

Differential Input Voltage:

±

5 VDC max.

Mark Condition:

≤ −

0.2 VDC

Space Condition:

≥ +

0.2 VDC

RS485 Drive Capability: Up to 32 RS485 receivers connected in parallel.
RS485 Drive Disable Time: 4 msec. max.

4. MAXIMUM CABLE LENGTH:

RS232: 50 feet
RS485: 4000 feet

5. BAUD RATE: 9600 min., 19200 max.
6. CERTIFICATIONS AND COMPLIANCES:

SAFETY

UL Recognized Component, File #E179259, UL3101-1, CSA C22.2 No.

1010-1
Recognized to U.S. and Canadian requirements under the Component
Recognition Program of Underwriters Laboratories, Inc.

IECEE CB Scheme Test Certificate # US/5141B/UL,

CB Scheme Test Report # 01ME11540-0702001

Issued by Underwriters Laboratories, Inc.

IEC 61010-1, EN 61010-1: Safety requirements for electrical

equipment for measurement, control and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Refer to EMC Installation Guidelines for additional information.

MODEL ICM4 - SERIAL CONVERTER MODULE (RS232C/RS485)

DIMENSIONS In inches (mm)

CAUTION: Risk of Danger.

Read complete instructions prior to

installation and operation of the unit.

Bulletin No. ICM4-D
Drawing No. LP0416
Released 3/07

Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net

UL Recognized Component,
File # E179259

900 MHz ± 5 MHz

Immunity to EN 50082-2

200 Hz, 50% duty cycle

Electrostatic discharge

EN 61000-4-2

Level 2; 4 Kv contact

Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3

Level 3; 10 V/m

80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4

Level 4; 2 Kv I/O

Level 3; 2 Kv power

RF conducted interference

EN 61000-4-6

Level 3; 10 V/rms

150 KHz - 80 MHz

Simulation of cordless telephone ENV 50204

Level 3; 10 V/m

Emissions to EN 50081-1

RF interference

EN 55022

Enclosure class B