5. CERTIFICATIONS AND COMPLIANCES:

SAFETY

IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment for
measurement, control, and laboratory use, Part 1.

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for Measurement,
Control and Laboratory use.

Notes:
1. Criterion A: Normal operation within specified limits.
2. Criterion B: Temporary loss of performance from which the unit self-

recovers.

3. This device was designed for installation in an enclosure. To avoid

electrostatic discharge to the unit in environments with static levels above
4 kV precautions should be taken when the device is mounted outside an
enclosure. When working in an enclosure (ex. making adjustments, setting
switches etc.) typical anti-static precautions should be observed before
touching the unit.

6. ENVIRONMENTAL CONDITIONS:

Operating Temperature Range: 0 to 50°C
Storage Temperature Range: -30 to +70°C
Operating and Storage Humidity: 80% max relative humidity,

non-condensing, from 0 to 50°C

Altitude: Up to 2000 meters

7. CONSTRUCTION: Case body is black high impact plastic and stainless

steel. Installation Category I, Pollution Degree 2.

8. POWER CONNECTION: Removable wire clamp screw terminal block.

Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)

9. MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting

rails according to EN50022 -35 x 7.5 and -35 x 15.

10. WEIGHT: 12.3 oz (348g)

HARDWARE

INSTALLATION

Figure 1 - Attach ICM8 To DIN Rail

POWER SUPPLY REQUIREMENTS

It is very important that the power supply is mounted correctly if the unit is

to operate reliably. Please take care to observe the following points:

– The power supply must be mounted close to the unit, with usually not more

than 6 feet (1.8 m) of cable between the supply and the ICM8. Ideally, the
shortest length possible should be used.

– The wire used to connect the ICM8’s power supply should be at least

22-gage wire. If a longer cable run is used, a heavier gage wire should be
used. The routing of the cable should be kept away from large contactors,
inverters, and other devices which may generate significant electrical
noise.

– A power supply with a Class 2 or SELV rating is to be used. A Class 2 or

SELV power supply provides isolation to accessible circuits from
hazardous voltage levels generated by a mains power supply due to single
faults. SELV is an acronym for “safety extra-low voltage.” Safety extra-
low voltage circuits shall exhibit voltages safe to touch both under normal
operating conditions and after a single fault, such as a breakdown of a layer
of basic insulation or after the failure of a single component has occurred.

2

1

Immunity to Industrial Locations:
Electrostatic discharge

EN 61000-4-2

Criterion B

3

4 kV contact discharge
8 kV air discharge

Electromagnetic RF fields

EN 61000-4-3

Criterion A
10 V/m

Fast transients (burst)

EN 61000-4-4

Criterion B
2 kV power
1 kV signal

Surge

EN 61000-4-5

Criterion A

RF conducted interference

EN 61000-4-6

Criterion A
3 V/rms

Emissions:
Emissions

EN 55011

Class A

1kV L-L,2 kV
L&N-E power