Red Lion AIMI User Manual
Specifications, Description, Voltage drop at input
MODEL AIMI - 0 (4) TO 20 MA PASSIVE LOOP POWERED ISOLATOR
SPECIFICATIONS
1. INPUT RANGE: 0(4) to 20 mA
2. MAXIMUM INPUT CURRENT/VOLTAGE: 40 mA/18 VDC
3. VOLTAGE DROP AT INPUT: 1.7 V + (20 mA * RLOAD)
4. MAXIMUM INPUT FREQUENCY: <75 Hz
5. RESPONSE TIME: 5 msec. max.
6. OUTPUT SIGNAL: 0(4) to 20 mA
Max. Load Resistance:
600
7. ISOLATION VOLTAGE: 1.5 KV, 50 Hz, for 1 minute
8. ACCURACY:
0.1% of full scale
9. OPERATING TEMPERATURE RANGE: -20 to +65 °C
10. TEMPERATURE COEFFICIENT:
0.002%/K of the measured value
11. CONSTRUCTION: Case body is black, Polyester PBT
12. MOUNTING: Standard DIN style rail, including top hat (T) profile rail
according to EN50022 - 35
7.5.
13. WEIGHT: 2 oz (56 g)
DESCRIPTION
The AIMI0202 passive isolator is used for the electrical isolation and
processing of analog 0(4) to 20 mA standard current signals. The AIMI0202
provides electrical isolation between the control electronics and process I/O. In
addition, interference signals above 75 Hz are effectively suppressed.
Input and output circuit do not require separate auxiliary power. The
AIMI0202 obtains power from the input signal. The modules are snapped onto
symmetrical DIN rails in accordance with EN 50022.
VOLTAGE DROP AT INPUT
When using the AIMI0202, ensure the voltage supply is sufficient for
handling both the voltage drop of the input and the output load voltage drop. The
AIMI0202 input resistance will create around a 1.7 V drop.
The following formula calculates the total voltage drop (input and output).
Total voltage drop = (1.7 V + (20 mA * RLOAD))
Where:
1.7 V = Input voltage drop
20 mA * RLOAD = Output load voltage drop
WIRING CONNECTIONS
Connect transducer to input (Terminals 1 & 2), observing polarity. A power
supply may be required for loop powered transducers.
The energy for the supply on the input side is taken from the analog input
signal. Due to the dynamic input resistance, a power loss of approximately 1.7 V
drops at the module input. The module’s output is self-powered (active), which
is also derived from the input signal.
4
3
2
1
5
6
7
8
1
2
3
4
0.24 (6.2)
4.00
(102.5)
3.66 (93.1)
POWER
SUPPLY
LOOP-POWERED
TRANSDUCER
ISOLATED
INPUT
IN I (+)
GND1 (-)
(+) OUT I
(-) GND2
(-)
(+)
(+)
(-)
1
2
6
5
(+)
(-)
R
LOAD
DIMENSIONS In inches (mm)
ORDERING INFORMATION
IN I
GND 1
GND 2
OUT I
1
2
5
6
RLOAD
I
I
0 (4)-20 mA
0 (4)-20 mA
AIMI
OUTPUT
INPUT
MODEL NO.
AIMI0202
PART NUMBER
Bulletin No. AIMI-X
Drawing No. LP0824
Effective 11/09
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
Red Lion Controls
Headquarters
20 Willow Springs Circle
York PA 17406
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
Red Lion Controls
China
Unit 101, XinAn Plaza
Building 13, No.99 Tianzhou Road
ShangHai, P.R. China 200223
Tel +86 21 6113-3688
Fax +86 21 6113-3683
Red Lion Controls
Europe
Printerweg 10
NL - 3821 AD Amersfoort
Tel +31 (0) 334 723 225
Fax +31 (0) 334 893 793
Red Lion Controls
India
54, Vishvas Tenement
GST Road, New Ranip,
Ahmedabad-382480 Gujarat, India
Tel +91 987 954 0503
Fax +91 79 275 31 350