beautypg.com

State GP6 75 YTPDT User Manual

Page 34

background image

34

NOTE: Do not allow insulation or other materials to accumulate

inside pipe assembly when installing through hole.

5. Secure assembly to roof structure as shown in “Figure: 27”

using field supplied metal strapping or equivalent support

material.

NOTE: Ensure termination height is above the roof surface or

anticipated snow level as shown in “Figure: 27”.

6. Install rain cap and small diameter pipe assembly in

roof penetration assembly, Ensure small diameter

pipe is cemented and bottomed in Y concentric fitting.

7. Cement water heater combustion air intake and vent pipes to

concentric vent termination assembly. See “Figure: 27” for

proper pipe attachment.

8. Operate heater through 1 heat cycle to ensure combustion

air and vent pipes are properly connected to concentric vent

termination connections.

FLAT ROOF INSTALLATION

When installing a concentric termination vertically through a flat

roof, the termination’s vent cap must be a minimum of 10 feet (3

m) away from any parapet, vertical wall or structure as shown

in Figure 27A.

If this required 10 foot (3 m) distance to a parapet, vertical wall

or structure cannot be maintained, standard terminations must

be used. See Vertical Termination Installation.

CONCENTRIC TERMINATION(S)

MUST BE A MINIMUM OF 10 FEET

(3 m) AWAY FROM ANY PARAPET,

VERTICAL WALL OR

STRUCTURE.

CONCENTRIC TERMINATION

FLAT ROOF CLEARANCE

Figure: 27A

INSTALLATION SIDE WALL TERMINATION

Figure: 28

1. Determine best location for termination kit.

NOTE: Consideration for the following should be used when

determining an appropriate location for the termination kit:

• Termination kit positioned where the vent vapors will not damage

plants/shrubs or air conditioning equipment.

• Termination kit positioned so it will not be affected by wind eddy

that may allow recirculation of combustion products, or airborne

leaves, or light snow.

• Termination kit positioned where it will not get damaged or be

subjected to foreign objects, such as stones, balls, etc.

• Termination kit positioned where the vent vapors will not be

objectionable.

NOTE: See Venting Installation section (starting on Page 25) in this

manual for additional vent location requirements.

2. Cut 1 hole (5 in. diameter).

3. Partially assemble concentric vent termination kit.

a) Cement the Y concentric fitting to larger diameter

kit pipe, see “Figure: 19”.

b) Cement the rain cap to the smaller diameter kit

pipe, see “Figure: 26”.

NOTE: Instead of cementing the smaller pipe to the rain cap, a

field-supplied stainless steel screw may be used to secure the 2

components together when field disassembly is desired for cleaning,

see “Figure: 26”.

When using alternate screw assembly method, drill clearance hole

in rain cap and pilot hole in vent pipe for screw being used. Failure

to drill adequate holes may cause cracking of PVC components,

allowing combustion products to be recirculated. Failure to follow

this warning could result in personal injury or death.

Do not operate the heater with rain cap removed or recirculation

of combustion products may occur. Water may also collect inside

larger combustion-air pipe and flow to the burner enclosure. Failure

to follow this warning could result in product damage or improper

operation, personal injury or death.

4. Install Y concentric fitting and pipe assembly through

structure’s hole.

NOTE: Do not allow insulation or other materials to accumulate

inside pipe assembly when installing through hole.

This manual is related to the following products: