TERMINATION CLEARANCES SIDEWALL DIRECT VENT

V

X

VENT TERMINAL

AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

v

v

A

G

V

FIXED

CLOSED

FIXED

CLOSED

OPERABLE

OPERABLE

V

C

B

B

B

B

F

B

V

V

A

J

V

H

M

X

X

V

V

K

B

E

D

L

DIRECT VENT

(using outdoor air for combustion)

EXTERIOR CLEARANCES FOR SIDEWALL VENT TERMINATION

Figure: 16

Vent terminal clearances for “Direct Vent” installations. Direct Vent configurations use outdoor air for combustion.

US INSTALLATIONS 1

US INSTALLATIONS 1

A

Clearance above grade,

veranda, porch, deck or

balcony

12 inches (30 cm)

H

Clearance to each side

of center line extended

above meter/regulator

assembly

3 feet (91 cm) within a height

15 feet (4.5 m) above the

meter/regulator assembly*

B

Clearance to window or

door that may be opened

6 inches (15 cm)

for appliances up to

10,000 Btu/hr (3 kW),

9 inches (23 cm) for

appliances between

10,000 Btu/hr (3 kW)

and 50,000 Btu/hr (15

kW), 12 inches (30 cm)

for appliances above

50,000 Btu/hr (15 kW)

I

Clearance to service

regulator vent outlet

3 feet (91 cm)*

C

Clearance to

permanently closed

window

6 inches (15 cm)*

J

Clearance to a non

mechanical air supply

inlet into building or

combustion air inlet to

any other appliance

6 inches (15 cm) for

appliances up to 10,000

Btu/hr (3 kW), 9 inches (23

cm) for appliances between

10,000 Btu/hr (3 kW) and

50,000 Btu/hr (15 kW), 12

inches (30 cm) for appliances

above 50,000 Btu/hr (15 kW)

D

Vertical clearance to

ventilated soffit located

above the terminal within

a horizontal distance of

2 feet (61 cm) from the

center line of the terminal

12 inches (30 cm)*

K

Clearance to a

mechanical air supply

inlet

3 feet (91 cm) above if within

10 feet (3 m) horizontally

E

Clearance to unventilated

soffit

12 inches (30 cm)*

L

Clearance above

paved sidewalk or

paved driveway located

on public property

7 feet (2.13 m)†*

F

Clearance to outside

corner

2 feet (60 cm)*

M

Clearance under

veranda, porch, deck,

or balcony

12 inches (30 cm) ‡*

G

Clearance to inside

corner

18 inches (45 cm)*

1 In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code.
† A vent shall not terminate where it may cause hazardous frost or ice accumulations on adjacent property surfaces.
‡ Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer’s installation instructions.