beautypg.com

Gas supply systems, Gas pressure requirements, Supply gas regulator – State GP6 75 YTPDT User Manual

Page 20

background image

20

GAS SUPPLY SYSTEMS

Low pressure building gas supply systems are defined as those

systems that cannot under any circumstances exceed 14” W.C. (1/2

PSI Gauge). These systems do not require pressure regulation.

Measurements should be taken to insure that gas pressures are

stable and fall within the requirements stated on the water heater

rating plate. Readings should be taken with all gas burning equipment

off (static pressure) and with all gas burning equipment running at

maximum rate (dynamic pressure). The gas supply pressure must

be stable within 1.5” W.C. from static to dynamic pressure to provide

good performance. Pressure drops that exceed 1.5” W.C. may cause

rough starting, noisy combustion or nuisance outages. Increases or

spikes in static pressure during off cycles may cause failure to ignite

or in severe cases damage to water heater gas control valves. If

your low pressure system does NOT meet these requirements, the

installer is responsible for the corrections.
High Pressure building supply systems use pressures that exceed

14” W.C. (1/2 PSI Gauge). These systems must use field supplied

regulators to lower the gas pressure to less than 14” W.C. (1/2 PSI

Gauge). Appliances require gas regulators that are properly sized

for the water heater input and deliver the rating plate specified

pressures. Gas supply systems where pressure exceeds 5 PSI often

require multiple regulators to achieve desired pressures. Systems in

excess of 5 PSI building pressure should be designed by gas delivery

professionals for best performance. Water heaters connected to gas

supply systems that exceed 14” W.C. (1/2 PSI Gauge) at any time

must be equipped with a gas supply regulator.

GAS PRESSURE REQUIREMENTS

All models require a minimum gas supply pressure of 3.5” W.C.(0.87

kPa) for natural gas and 8.0” W.C. (1.99 kPa) for propane. The

minimum supply pressure is measured while gas is not flowing

(static pressure) AND while gas is flowing (dynamic pressure). The

supply pressure (static and dynamic) should never fall below 3.5”

W.C.(0.87 kPa) for natural gas or 8.0” W.C. (1.99 kPa) for propane.

The supply pressure should be measured with all gas fired water

heaters connected to the common main firing at full capacity. If the

supply pressure drops more than 1.5” W.C. (0.37 kPa) as gas begins

to flow to the water heater then the supply gas system including the

gas line and/or the gas regulator may be restricted or undersized.

See Supply Gas Regulator section and Gas Piping section of this

manual. The gas control valve on all models has a maximum gas

supply pressure limit of 14” W.C.(3.48 kPa) The maximum supply

pressure is measured while gas is not flowing (static pressure) AND

while gas is flowing (dynamic pressure).

SUPPLY GAS REGULATOR

The maximum allowable gas supply pressure for this water heater

is 14 inches W.C. (3.5 kPa). Install a positive lock-up gas pressure

regulator in the gas supply line if inlet gas pressure can exceed 14

inches W.C. (3.5 kPa) at any time. Regulators must be sized/used

according to manufacturer’s specifications.
If a positive lock-up regulator is required follow these instructions:
1. Positive lock-up gas pressure regulators must be rated at or above

the input Btu/hr rating of the water heater they supply.

2. Positive lock-up gas pressure regulator(s) should be installed no

closer than 3 feet (1 meter) and no farther than 8 feet (2.4 meters)

from the water heater’s inlet gas connection.

3. After installing the positive lock-up gas pressure regulator(s) an

initial nominal supply pressure setting of 7.0” W.C.(1.74 kPa) for

Natural Gas and 11.0” W.C. (2.74 kPa) for Propane (LP) while

the water heater is operating is recommended and will generally

provide good water heater operation. Some additional adjustment

may be required later to maintain a steady gas supply pressure.

4. When installing multiple water heaters in the same gas supply

system it is recommended that individual positive lock-up gas

pressure regulators be installed at each unit.

All gas piping must comply with local codes and ordinances or with

the current editions National Fuel Gas Code (ANSI Z223.1/ NFPA-

54). Copper or brass tubing and fittings (except tin lined copper

tubing) shall not be used.
If the gas control valve is subjected to pressures exceeding 1/2 psi

(3.5 kPa), the damage to the gas control valve could result in a fire

or explosion from leaking gas.
If the main gas line Shut-off serving all gas water heaters is used,

also turn off the gas at each water heater. Leave all gas appliances

shut off until the water heater installation is complete.
A gas line of sufficient size must be run to the water heater. Consult

the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA

54) and your gas supplier concerning pipe size.
There must be:
• A readily accessible manual shut off valve in the gas supply line

serving the water heater, and

• A sediment trap ahead of the gas control valve to help prevent dirt

and foreign materials from entering the gas control valve.

• A ground joint union of proper size between the manual shut off

valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water

heater. Use a soapy water solution, not a match or open flame.

Rinse off soapy solution and wipe dry.

This manual is related to the following products: