beautypg.com

Insulation blankets, Combustion air and ventilation – State GP6 75 YTPDT User Manual

Page 15

background image

15

Minimum clearances between the water heater and combustible

construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from

the front and 18” (45.7 cm) from the top. (Standard clearance.) If

clearances stated on the heater differ from standard clearances, install

water heater according to clearances stated on the heater.

Adequate clearance 30” (76 cm) for servicing this water heater should

be considered before installation, such as changing the anode rods,

control system components and gas control valve.

A minimum clearance of 5.5” (14.0 cm) must be allowed for access to

replaceable and/or serviceable parts such as the thermostats, drain valve,

condensate drain, temperature-pressure relief valve, clean out opening,

and the vent connection (exhaust elbow).

When installing the heater, consideration must be given to proper

location. Location selected should be as close to the wall as practicable

and as centralized with the water piping system as possible.

Figure 3: CLEARANCES

INSULATION BLANKETS

Insulation blankets are available to the general public for external use

on gas water heaters but are not necessary with these products. The

purpose of an insulation blanket is to reduce the standby heat loss

encountered with storage tank heaters. Your water heater meets or

exceeds the Energy Policy Act standards with respect to insulation and

standby loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you

should follow these instructions (For identification of components

mentioned below, see “Figure 1B: 50 GALLON UNIT” & “Figure 1C:

75 GALLON UNIT”. Failure to follow these instructions can restrict

the air flow required for proper combustion, potentially resulting in

fire, asphyxiation, serious personal injury or death.

• Do not apply insulation to the top of the water heater, as this will

interfere with safe operation of the blower assembly.

• Do not cover the control system LCD on top of the water heater.

• Do not cover the outer door, thermostat or temperature & pressure

relief valve.

• Do not cover the instruction manual. Keep it on the side of the

water heater or nearby for future reference.

• Do obtain new warning and instruction labels from the manufacturer

for placement on the blanket directly over the existing labels.

• Do inspect the insulation blanket frequently to make certain it does

not sag, thereby obstructing combustion air flow.

COMBUSTION AIR AND VENTILATION

A gas water heater cannot operate properly without the correct

amount of air for combustion. Do not install in a confined area such

as a closet, unless you provide air as shown in the Facts to Consider

About Location section. Never obstruct the flow of ventilation air. If

you have any doubts or questions at all, call your gas supplier. Failure

to provide the proper amount of combustion air can result in a fire or

explosion and cause death, serious bodily injury, or property damage.

Figure 4: COMBUSTION AIR AND VENTILATION

If this water heater will be used in beauty shops, barber shops,

cleaning establishments, or self-service laundries with dry cleaning

equipment, it is imperative that the water heater(s) be installed

direct vent so that all air for combustion and ventilation is taken

from outdoors.

Propellants of aerosol sprays and volatile compounds, (cleaners,

chlorine based chemicals, refrigerants, etc.) in addition to being

highly flammable in many cases, will also react to form corrosive

hydrochloric acid when exposed to the combustion products of

the water heater. The results can be hazardous, and also cause

product failure.

This manual is related to the following products: