Materials required, Tools (use insulated tools only), Accessories – Outback Power Systems EnergyCell RE Battery Owners Manual User Manual
Page 7: Storage and environment requirements, Temperatures, Self-discharge, Tools, Energycell batteries, Figure 4 energycell gh shelf life, Caution: fire hazard

EnergyCell Batteries
900-0127-01-00 Rev D
7
Materials Required
Tools (use insulated tools only)
Torque wrenches
Voltmeter
Accessories
Interconnect bar (provided with front terminal batteries only)
Terminal cover (provided with front terminal batteries only)
Hardware kit
Interconnect cables as needed
CAUTION: Fire Hazard
Install properly sized battery cabling and interconnect cables. The cable
ampacity must meet the needs of the system, including temperature, deratings,
and any other code concerns.
Storage and Environment Requirements
Temperatures
EnergyCell batteries should not be operated in an environment where the average ambient
temperature exceeds 85°F (27°C). The peak temperature of the operating environment should not
exceed 110°F (43°C) for a period of more than 24 hours. High operating temperatures will shorten a
battery’s life (see page 8).
Do not allow batteries to freeze, as this will damage them and could result in leakage.
Do not expose batteries to temperature variations of more than 5°F (3°C). This leads to voltage
imbalance between multiple batteries (or between battery cells if there is a temperature differential).
Batteries should be stored in a cool, dry location. Place them in service as soon as possible. The best
storage temperature is 77°F (25°C), but a range of 60°F (16°C) to 80°F (27°C) is acceptable.
Self-Discharge
All EnergyCell batteries will discharge over time once charged, even in storage. Higher storage temperatures
increase the rate of self-discharge. The EnergyCell GH has a longer shelf life than other VRLA batteries,
including the EnergyCell RE. At room temperature (77°F or 25°C), the EnergyCell GH has a shelf life of 18 months
before self-discharging to unacceptable levels. Figure 4
shows the rate of EnergyCell GH self-discharge at
various temperatures.
Fully charged, the natural (“rest”) voltage of all
EnergyCell batteries is approximately 12.8 Vdc.
A battery should have a freshening charge (see
pages 14 and 15) if its rest voltage is below
12.5 Vdc per battery (2.08 Vdc per cell).
A battery should not be used if its rest voltage
is 12.0 Vdc or lower upon delivery. Contact the
vendor upon receiving a battery in this state.
No EnergyCell should
ever be permitted to
self-discharge below 70% state of charge
(SoC). Such as condition is highly detrimental
and will shorten battery life. (This situation is
not the same as discharging to 70% SoC or
lower under load. See page 8.)
Figure 4 EnergyCell GH Shelf Life
0
6
12
18
24
30
36
42
48
Months
2.17
2.16
2.15
2.14
2.13
2.12
2.11
2.10
Res
t V
olt
s p
er
c
ell
A
pp
ro
xim
at
e
%
St
at
e o
f C
har
ge
100
96
91
87
83
79
74
70
40°C
104°F
30°C
86°F
25°C
77°F
20°C
68°F
10°C
50°F