The Radian cannot take voltage other than 120/240 Vac. If wires are 120 Vac each, but do not measure

240 Vac from one to the next (such as two legs of a 3-phase source), it will not accept the power.
The AC source(s) can power both battery charger and loads if sized correctly. Use the source

amperage to determine actual maximum draw. Size input circuit breakers accordingly.
The terminals labeled

L1 and L2 Out are used to connect the Radian inverter to the load circuits.

These terminals also transfer power from an input source if it is available. They can carry up to 55

amps using the inverter’s transfer relay. Size load circuit breakers accordingly.
Three

Neu terminals are available. These terminals are electrically common. Any of them can be used

to connect to neutral wires from various parts of the system. The most common connections are to

the neutral bus on the main panel or utility grid service, the neutral bus on the output load panel, the

neutral bus in the GSLC, and the neutral wire from a generator.
A Ground TBB is also available if multiple ground connections are needed (see

Figure 13 on page 24).

AC Sources

The inverter’s transfer relay is normally set to provide inverter power to the output. When an AC

source is present and accepted, the transfer relay switches to transfer the AC source power to the

loads. (See the Radian Series Inverter/Charger Operator’s Manual for the inverter’s acceptance criteria.)
The Radian inverter has connections for two AC sources for ease of installation. Each source is

transferred with a separate relay. However, internally it can only connect to one AC source at a time. It

cannot use both utility grid and generator power at the same time. If presented with two sources of

power, its default setting is to accept utility grid. (See the MATE3 manual for instructions on changing

the source priority.)

Figure 16 AC Sources

The arrow between the output neutral and ground wires indicates that these two wires have been

bonded together, usually at the main electrical panel. Only one bond should be made between
neutral and ground at any time. See page 26. If a generator is present in a building-based installation,

the generator’s neutral and ground should be isolated.