Installation, Location and environmental requirements, Dimensions – Outback Power Systems GS8048 Installation Manual User Manual
Page 19

17
Installation
Location and Environmental Requirements
Radian Series Inverter/Chargers must be located in a weather-proof enclosure or enclosed area. These
inverters are not designed for exposure to water or excessive wind-blown dust and debris.
The Radian inverter must be wall-mounted in an upright position. The inverter is not approved for
mounting in any other position or orientation.
Recommended minimum clearance is 2 to 4 inches (5 to 10 cm) for the front and top of the inverter.
The sides and bottom may be enclosed or obscured with no restriction when mounting accessory devices or 
one other Radian Series Inverter/Charger. If more than two Radian inverters are installed side by side with 
the GSLC, the inverters should be separated by at least 0.9 inches (2.3 cm) to accommodate the GSLC doors. 
The Radian inverter will function best if operated in a temperature range of 32°F to 77°F (–20°C to 25°C). At 
temperatures up to 122°F (50°C), all inverter components meet their specifications, but the inverter’s power 
is derated. It can function in environments as cold as –40°F (–40°C) and as warm as 140°F (60°C), but it may 
not meet all component specifications. This temperature range also applies to storage. 
The specifications are listed in the Radian Series Inverter/Charger Operator’s Manual.
Dimensions
Figure 6 Dimensions
Enclosure Height 
28” (71.1 cm) 
Width 16” (40.6 cm)
Depth
8.75” (22 cm)
Enclosure
Height with
Flange
29.13”
(74 cm)