Grounding

WARNING: Shock Hazard

The unit must be connected to a grounded, permanent wiring system. If a bond is made

between neutral and ground, make sure only one bond is present in the AC system at any
time. Some codes require the bond to be made at the main panel only. (The GSLC is

equipped with its own bond, which may need to be removed.)

WARNING: Shock Hazard

For all installations, the negative battery conductor should be bonded to the grounding

system at only one point. If the OutBack GFDI is present, it can provide the bond. (The

GSLC is also equipped with its own bond, which may need to be removed.)

IMPORTANT:

OutBack products are not designed for use in a positive-grounded system. If it is

necessary to build this system with OutBack products, contact OutBack Technical Support

at

+1.360.618.4363 before proceeding. Additionally, consult the online forum at

www.outbackpower.com/forum/, where this subject has been discussed extensively.

Table 3 Ground Conductor Size and Torque Requirements

Terminal Location

Minimum Conductor Size Torque Requirements

Ground TBB

#8 AWG (0.013 in²) or 10 mm²

25 in-lbs/2.8 Nm


Figure 13 Chassis Ground TBB

The inverter’s ground terminal bus bar (TBB) is used for

making all ground connections to other parts of the

system. Examples include inverter equipment grounding,
generator grounding, load panel grounding, and main

earth ground wire.
This TBB accepts up to #4 AWG (0.033 in²) or 25 mm²wire.